7.2 Modbus TCP technical specifications

Number of IO socket connections
Maximum number of IO data
Function codes supported
Diagnostics
DHCP
Watchdog
Certificate
To optimise data security when using Modbus TCP
via a cellular router, Grundfos strongly recommends
that the cellular data connection is based on a private
APN with static IP and with no access to public
Internet.

7.3 BACnet IP technical specifications

Number of IO socket connections
Communication
Maximum number of IO data
Objects supported
DHCP
Foreign device
8
255 bytes per telegram
03 Read holding registers
04 Read input registers
06 Write single registers
16 Write multiple registers
No
Supported
Communication watchdog with fixed 5 seconds time-out.
It can be enabled via the watchdog register in the device
profile.
No
1
User Datagram Protocol, UDP
1500 bytes
Analog input
Analog output
Analog value
Binary input
Binary output
Multistate input
Multistate output
Device
Supported
Supported