Herunterladen Inhalt Inhalt Diese Seite drucken

Grm Ip - Grundfos CIM 500 Montage- Und Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 27
6.4 GRM IP / GiC
You can detect faults in a module by observing the
status of the two status LEDs.
The prerequisite is that CIM 500 is fitted in a
Grundfos product or in a CIU 500. This requires a
contract with Grundfos.
6.4.1 Both LEDs remain off
Both LEDs remain off when the power supply is connected.
Cause
The module is fitted incorrectly in the Grundfos
product.
The module is defective.
CIU 500 is defective.
6.4.2 LED1 is off
Cause
SW1 is not set correctly.
6.4.3 LED2 is flashing red
Cause
No internal communication between the module and
the Grundfos product.
No internal communication between CIU 500 and the
Grundfos product.
6.4.4 LED1 is flashing green
Cause
120 seconds startup phase.
6.4.5 LED1 is permanently red
Cause
SW1 is in an illegal position.
6.4.6 LED2 is permanently red
Cause
The module does not support the connected
Grundfos product.
6.4.7 LED1 is flashing red
Cause
The GRM IP / GiC communication is lost or there is
no communication to the server.
Ensure that SW1 is in position "4" to select
GRM IP or position "5" to select GiC.
Remedy
Check that the module is fitted and connected
correctly.
Replace the module.
Replace CIU 500.
Remedy
Set the switch to "4" for GRM IP and to "5" for GiC.
Remedy
Check that the module is fitted correctly in the
Grundfos product.
Check the cable connection between the Grundfos
product and CIU 500.
Check that the individual conductors are connected
correctly, for example, not reversed.
Check the power supply to the Grundfos product.
Remedy
-
Remedy
Set the switch to "4" or "5".
Remedy
Contact the nearest Grundfos company.
Remedy
Check the Ethernet cable in the router.
Check the router settings.
Check the router related to the SIM card.
19

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis