3.3 Selection of Industrial Ethernet protocol

The module has a rotary switch for selection of the
Industrial Ethernet protocol. See the figure below.
Selecting the Industrial Ethernet protocol
Pos.
Description
0
PROFINET IO, default
1
Modbus TCP
2
BACnet IP
3
EtherNet/IP
GRM IP for Grundfos Remote
4
Management. Requires a contract with
Grundfos.
5
Grundfos iSOLUTIONS Cloud (GiC)
Reserved. LED1 is permanently red to
6...E
indicate an invalid configuration.
Resetting to factory settings.
Set the rotary switch to this position.
LED1 starts flashing red and green for 20
seconds to indicate that factory reset is
about to take place.
F
After 20 seconds, LED1 stops flashing and
factory reset is initiated.
When both LED1 and LED2 switch off, the
reset is completed. The rotary switch can
be moved to another position.
If the position of the rotary switch is
changed when the module is powered on,
the module restarts and uses the protocol
associated with the new position.
Related information
2. Applications

3.4 Setting the IP addresses

The module comes with a fixed webserver IP
address. Via the webserver, this address can be
changed to another fixed value, or a DHCP server
can be selected.
IP address: 192.168.1.100
Default IP settings
used
Subnet mask: 255.255.255.0
by the webserver
Gateway: 192.168.1.1
The device name is configured
from the webserver or from the
PROFINET IO configuration
Device name and
tool. The IP address is
IP settings for
automatically assigned by the
PROFINET IO
PLC. This assigned PROFINET
IP address must be different
from the webserver's IP
address.
It can be given a fixed value via
the webserver, or it can use a
DHCP server.
IP settings for
Modbus TCP
This assigned Modbus TCP
address must be different from
the webserver's IP address.
It can be given a fixed value via
the webserver, or it can use a
IP settings for
DHCP server. Note that BACnet
BACnet IP
IP and the webserver share the
same IP address.
It can be given a fixed value via
the webserver, or it can use a
DHCP server.
IP settings for
EtherNet/IP
This assigned EtherNet/IP
address must be different from
the webserver's IP address.
GiC uses DHCP, and the
IP settings for GiC
connected router automatically
assigns an IP address.
9