Installation
2.3.3 UL
UL recognized component to UL 61010B-1.
!
Note!
The UL applies only for the compact thermometers TMR31, TMR35 with electronics and 4 to
20 mA output signal.
3
Installation
3.1
Incoming acceptance, transport, storage
3.1.1 Incoming acceptance
On receipt of the goods, check the following points:
• Are the contents or the packaging damaged?
• Is the delivery complete and is anything missing? Check the scope of delivery against your
order.
3.1.2 Transport and storage
Note the following points:
• Pack the device in such a way as to protect it reliably against impact for storage (and
transportation).
• The permitted storage temperature is: -40 to +85 °C (-40 to 185 °F).
3.2
Installation instructions
3.2.1 General information
• Permitted ambient temperature range: -40 to 85 °C (-40 to 185 °F)
• Process temperature limits:
without extension neck: -50 to 150 °C (-58 to 302 °F)
with extension neck: -50 to 200 °C (-58 to 392 °F)
without transmitter: -50 to 200 °C (-58 to 392 °F)
Restrictions of TMR31 subject to the ambient temperature (recommended guideline values):
max. ambient temperature
up to 25 °C (77 °F)
up to 40 °C (104 °F)
up to 60 °C (140 °F)
up to 85 °C (185 °F)
20
max. process temperature
without extension neck
150 °C (302 °F)
135 °C (275 °F)
120 °C (248 °F)
100 °C (212 °F)
TMR31, TMR35
with extension neck
200 °C (392 °F)
180 °C (356 °F)
160 °C (320 °F)
133 °C (271 °F)
Endress+Hauser