York Saphir YSF Gebrauchs - Und Wartungsanweisungen Seite 26

Gebläsekonvektoren
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

It is a mandatory:
1
to use water or a mixture of water and propylene or ethylene glycol to feed the heat exchanger.
Maximum glycol content 50%.
Installation sites to avoid:
2
moist rooms or places where the unit may get in contact with water sprays (laundries,
bathrooms, etc.);
areas exposed to direct sunshine or too close to heating sources (lamps etc.);
3
rooms where the following substances might be present: flammable gas, alkaline material
or oil vapours;
positions where the air intake or air outlet might be obstructed (by shelving, furniture etc.);
4
in areas with risks of explosion or with severely dusty air.
The installation of the fan coil must assure:
safe use and working: the unit has not to cause any damage or danger to persons, objects
or animals;
5
a regular air circulation in the room;
the air intake and outlet are not obstructed in any way;
the respect of the minimum space necessary for installation and maintenance operations
6
(see below);
7
8
9
10
Mod.
+
YSIH
Before proceeding with any
operation of installation and/or
maintenance, make sure that the
unit has been disconnected from
the power supply
26
D
Size
A
20-40
85
(Fig. 2).
C
B
E
B
C
mm
205
190
Fig. 2
A
D
E
200
200