Herunterladen Inhalt Inhalt Diese Seite drucken

WIKA GDM-100-T Betriebsanleitung Seite 25

Hybrid-gasdichtewächter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5. Commissioning, operation
Register
Parameter
00110
HW version
00111
SW version
00112
Model description
00113
TAG number (name of gas density
sensor)
Gas mixture SF
00160
00161
Gas mixture N
00162
Gas mixture CF
00163
Gas mixture O
00164
Gas mixture CO
00165
Gas mixture 3M™ Novec™ 4710
00166
Gas mixture He
00167
Gas mixture Ar
Address
The available address space is 1 ... 247 (standard 247).
Baud rate
The different speeds are presented with register values 0 ... 8.
Baud rate
Register value
1,200
0
2,400
1
4,800
2
9,600
3
14,400
4
19,200
5 (standard)
38,400
6
57,600
7
115,200
8
Parity
Parity
Register value
None
0 (standard)
1
Even
WIKA operating instructions, model GDM-100-T
Value definition
2 = model GD-20-D
16 byte ASCII
0 ... 100 %
6
0 ... 100 %
2
0 ... 100 %
4
0 ... 100 %
2
0 ... 100 %
2
0 ... 100 %
0 ... 100 %
0 ... 100 %
Standard
Writable
Read only
Read only
Read only
Yes
100 %
Read only
0 %
Read only
0 %
Read only
0 %
Read only
0 %
Read only
0 %
Read only
0 %
Read only
0 %
Read only
25
EN

Werbung

Kapitel

Inhaltsverzeichnis
loading