5. Commissioning, operation
Register
Parameter
00110
HW version
00111
SW version
00112
Model description
00113
TAG number (name of gas density
sensor)
Gas mixture SF
00160
00161
Gas mixture N
00162
Gas mixture CF
00163
Gas mixture O
00164
Gas mixture CO
00165
Gas mixture 3M™ Novec™ 4710
00166
Gas mixture He
00167
Gas mixture Ar
Address
The available address space is 1 ... 247 (standard 247).
Baud rate
The different speeds are presented with register values 0 ... 8.
Baud rate
Register value
1,200
0
2,400
1
4,800
2
9,600
3
14,400
4
19,200
5 (standard)
38,400
6
57,600
7
115,200
8
Parity
Parity
Register value
None
0 (standard)
1
Even
WIKA operating instructions, model GDM-100-T
Value definition
2 = model GD-20-D
16 byte ASCII
0 ... 100 %
6
0 ... 100 %
2
0 ... 100 %
4
0 ... 100 %
2
0 ... 100 %
2
0 ... 100 %
0 ... 100 %
0 ... 100 %
Standard
Writable
Read only
Read only
Read only
Yes
100 %
Read only
0 %
Read only
0 %
Read only
0 %
Read only
0 %
Read only
0 %
Read only
0 %
Read only
0 %
Read only
25
EN