5. Commissioning, operation
5.3.2 Pin assignment of attached, digital transmitter (model GD-20-D)
Circular connector M12 x 1 (5-pin)
1
-
2
U
+
3
U
-
4
A
5
B
5.3.3 Pin assignment of integrated, digital transmitter (model GD-20-D)
Modbus
-RTU via RS-485 interface in rear cable socket
®
Rear cable socket
1
-
-
2
U
DC 10 ... 30 V
+
3
U
Ground
-
4
A
RS-485 signal
5
B
RS-485 signal
6
-
-
5.3.4 Requirements for shielding and grounding
Only use shielded cables and connect the shield on one side to the read-out unit.
The gas density sensor is grounded via the process connection of the mechanical
base instrument.
Ensure that no earth circuits can occur.
5.3.5 RS-485
The physical layer for the Modbus
TIA-485. The differential signal between pins 4 and 5 (A and B) is evaluated with a
2-wire system (half-duplex).
5.4
Modbus
®
The Modbus
communication protocol is based on a master/slave architecture. The
®
protocol implemented in the model GD-20 gas density sensor is Modbus
transmission via a 2-wire RS-485 interface.
The Modbus
protocol is a single-master protocol. This master controls the entire data
®
transfer and monitors any possible timeouts (no reply from the addressed instrument).
The connected instruments may only send telegrams after request by means of the
master.
WIKA operating instructions, model GDM-100-T
-
Supply voltage
Ground
Signal RS-485
Signal RS-485
protocol is the serial RS-485 interface per EIA/
®
EN
-RTU with serial
®
19