Micropulse Transducer - Rod Style
8
Calibration using adjustment (continued)
4. Adjust end value
Bring magnet to end position.
Hold down
for at least 2 s.
Indication for "Adjust end value" is displayed.
Adjust end value
The end value can be changed using
and
1)
. The gradient of the output
is changed, but the zero value remains
unchanged (see page 16).
Exit calibration procedure: Press
more than 2 s.
Indication for "Adjustment" is displayed.
Set position value is saved.
Check values
The settings for the start value and end
value have a mutual effect depending
on the measuring position.
Repeat steps 3 and 4 until the desired
values are exactly set.
5. Exit adjustment and deactivate buttons
Hold down
and
Output indicates error value.
Briefly press
or
Buttons are deactivated.
Current position value is displayed.
1) Briefly press button: Current value is increased or
decreased by approx. 1 mV or 1  A.
If a button is held down longer than 1 s, the step
interval is increased.
20
english
All manuals and user guides at all-guides.com
and
for no
simultaneously for at least 6 s.
(< 1 s).
LED legend:
Adjust
start value
LED display
(see page 19)
LED1 LED2 At 0 to 10 V
> 2 s
2
1
1
2
2
1
2
< 2 s
1
2
> 6 s
1
2
< 1 s
LED not on
LED green
LED 1 and LED 2 flashing red-green in alternation
LED flashing green
LED 1 and LED 2 flashing red-red in alternation
Displayed values (example)
At 4 to 20 mA
9.89 V
19.13 mA
10.00 V
20.00 mA
9.89 V
19.13 mA
9.00 V
19.00 mA
2.00 V
6.00 mA
9.00 V
19.00 mA
10.50 V
3.60 mA
9.00 V
19.00 mA