Herunterladen Inhalt Inhalt Diese Seite drucken

Elektro-Automatik PS 9000 1U Betriebsanleitung Seite 96

Dc-labornetzgerät
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

PS 9000 1U Series
3.5.4.4
Analog interface specification
Pin Name
Type* Description
1
VSEL
AI
Set voltage value
2
CSEL
AI
Set current value
3
VREF
AO
Reference voltage 10 V or 5 V
Ground for all
4
DGND
POT
digital signals
Switching internal /
5
REMOTE
DI
remote control
Overheating or
6
OT
DO
power fail*** alarm
7
-
-
-
8
PSEL
AI
Set power value
9
VMON
AO
Actual voltage
10 CMON
AO
Actual current
Ground for all
11 AGND
POT
analog signals
12 -
-
-
DC output OFF
13 REM-SB
DI
(DC output ON)
(ACK alarms ****)
14 OVP
DO
Overvoltage alarm
Constant voltage
15 CV
DO
regulation active
* AI = Analog Input, AO = Analog Output, DI = Digital Input, DO = Digital Output, POT = Potential
** Internal Vcc approx. 14.3 V
*** Mains blackout, mains overvoltage or PFC error
***** The error of a set value input adds to the general error of the related value on the DC output of the device
The accuracy of set values, as given in the table above, is only related to the input pin and adds
to the general accuracy of the corresponding value on the DC output (see technical specs)
3.5.4.5
Overview of the Sub-D Socket
EA Elektro-Automatik GmbH
Page 40
Helmholtzstr. 31-33 • 41747 Viersen
Germany
Default levels
0...10 V or. 0...5 V corre-
spond to 0..100% of U
Nom
0...10 V or. 0...5 V corre-
spond to 0..100% of I
Nom
Remote = LOW, U
<1 V
Low
Internal = HIGH, U
>4 V
High
Internal = Open
Alarm OT= HIGH, U
> 4 V
High
No Alarm OT= LOW, U
<1
Low
V
-
0...10 V or. 0...5 V corre-
spond to 0..100% von P
Nom
0...10 V or. 0...5 V corre-
spond to 0..100% von U
Nom
0...10 V or. 0...5 V corre-
spond to 0..100% von I
Nom
-
Off = LOW, U
<1 V
Low
On= HIGH, U
>4 V
High
On = Open
Alarm OV = HIGH, U
> 4 V
High
No alarm OV = LOW, U
<1 V
Low
CV = LOW, U
<1 V
Low
CC/CP = HIGH, U
>4 V
High
**** Only during remote control
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
Electrical specification
Accuracy 0-5 V range: < 0.4% *****
Accuracy 0-10 V range: < 0.2% *****
Input impedance R
>40 k...100 k
i
Tolerance < 0.2% at I
= +5 mA
max
Short-circuit-proof against AGND
For control and status signals.
Voltage range = 0...30 V
I
= -1 mA bei 5 V
Max
U
= 3 V
LOW to HIGH typ.
Rec'd sender: Open collector against DGND
Quasi open collector with pull-up against Vcc **
With 5 V on the pin max. flow +1 mA
I
= -10 mA at U
= 0,3 V
CE
Max
U
= 30 V
Max
Short-circuit-proof against DGND
-
Accuracy 0-5 V range: < 0.4% *****
Accuracy 0-10 V range: < 0.2% *****
Input impedance R
>40 k...100 k
i
Accuracy < 0.2% at I
= +2 mA
Max
Short-circuit-proof against AGND
For -SEL, -MON, VREF Signals
-
Voltage range = 0...30 V
I
= +1 mA at 5 V
Max
Rec'd sender: Open collector against DGND
Quasi open collector with pull-up against Vcc **
With 5 V on the pin max. flow +1 mA
I
= -10 mA at U
= 0,3 V, U
CE
Max
Short-circuit-proof against DGND
www.elektroautomatik.de
ea1974@elektroautomatik.de
= 30 V
Max

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis