PS 9000 1U Series
3000 W
AC Input
Input voltage
Input connection
Input fuse (internal)
Leak current
Power factor
Idle mode power consumption
DC Output
Max. output voltage U
Max
Max. output current I
Max
Max. output power P
Max
Overvoltage protection range
Overcurrent protection range
Overpower protection range
Temperature coefficient
Output capacitance (approx.)
Voltage regulation
Adjustment range
Accuracy
(at 23 ± 5°C)
(1
Line regulation at ±10% ΔU
Load regulation at 0...100% load < 0.05% U
Rise time 10...90% ΔU
Transient time after load step
Display: Resolution
Display: Accuracy
(3
Ripple
(2
Remote sensing compensation
Fall time (at no load) after
switching DC output off
Current regulation
Adjustment range
Accuracy
(at 23 ± 5°C)
(1
Line regulation at ±10% ΔU
Load regulation at 0...100% ΔU
Ripple
(2
Display: Resolution
Display: Accuracy
(3
Power regulation
Adjustment range
Accuracy
(at 23 ± 5°C)
(1
Line regulation at ±10% ΔU
Load regulation at 10-90% ΔU*ΔI < 0.75% P
Display: Resolution
Efficiency at 100% U
DC
Efficiency at 100% I
DC
(1 Related to the nominal values, the accuracy defines the maximum deviation between an adjusted values and the true (actual) value.
Example: a 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20MHz
(3 The display error adds to the error of the related actual value on the DC output
EA Elektro-Automatik GmbH
Page 12
Helmholtzstr. 31-33 • 41747 Viersen
Germany
PS 9080-100
PS 9200-50
207...264 V AC, 45...66 Hz
1ph (L, N, PE)
T16 A
< 3.5 mA
~ 0.99
~ 70 W
80 V
200 V
100 A
50 A
3000 W
3000 W
0...88 V
0...220 V
0...110 A
0...55 A
0...3300 W
0...3300 W
Voltage / current: 100 ppm/K
8930 μF
1500 μF
0...81.6 V
0...204 V
< 0.1% U
< 0.1% U
Nenn
< 0.02% U
< 0.02% U
AC
Nenn
< 0.05% U
Nenn
Max. 15 ms
Max. 15 ms
< 1.7 ms
< 1.4 ms
See section „1.9.4.4. Resolution of the displayed values"
≤ 0.2% U
≤ 0.2% U
Nom
< 76 mV
< 234 mV
PP
< 4.2 mV
< 40 mV
RMS
Max. 5% U
Max. 5% U
Nom
Down from 100% to <60 V: less than 10 s
0...102 A
0...51 A
< 0.2% I
< 0.2% I
Nenn
< 0.05% I
< 0.05% I
AC
Nenn
< 0.15% I
< 0.15% I
OUT
Nenn
< 114 mA
< 29 mA
PP
See section „1.9.4.4. Resolution of the displayed values"
≤ 0.2% I
≤ 0.2% I
Nom
0...3060 W
0...3060 W
< 1% P
< 1% P
Nenn
< 0.05% P
< 0.05% P
AC
Nenn
< 0.75% P
Nenn
See section „1.9.4.4. Resolution of the displayed values"
~ 91%
~ 93%
~ 89%
~ 90%
Model 1U
PS 9360-30
360 V
30 A
3000 W
0...396 V
0...33 A
0...3300 W
705 μF
0...367.2 V
< 0.1% U
Nenn
Nenn
< 0.02% U
Nenn
Nenn
< 0.05% U
Nenn
Nenn
Max. 15 ms
< 2.2 ms
≤ 0.2% U
Nom
Nom
< 156 mV
PP
PP
< 26 mV
RMS
RMS
Max. 5% U
Nom
Nom
0...30.6 A
< 0.2% I
Nenn
Nenn
< 0.05% I
Nenn
Nenn
< 0.15% I
Nenn
Nenn
< 10 mA
PP
PP
≤ 0.2% I
Nom
Nom
0...3060 W
< 1% P
Nenn
Nenn
< 0.05% P
Nenn
Nenn
< 0.75% P
Nenn
Nenn
~ 94%
~ 92%
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
PS 9500-20
PS 9750-12
500 V
750 V
20 A
12 A
3000 W
3000 W
0...550 V
0...825 V
0...22 A
0...13,2 A
0...3300 W
0...3300 W
150 μF
70 μF
0...510 V
0...765 V
< 0.1% U
< 0.1% U
Nenn
Nenn
< 0.02% U
< 0.02% U
Nenn
< 0.05% U
< 0.05% U
Nenn
Max. 15 ms
Max. 15 ms
< 2 ms
< 2 ms
< 234 mV
< 260 mV
PP
PP
< 50 mV
< 40 mV
RMS
RMS
Max. 5% U
Max. 5% U
Nom
0...20.4 A
0...12.24 A
< 0.2% I
< 0.2% I
Nenn
Nenn
< 0.05% I
< 0.05% I
Nenn
Nenn
< 0.15% I
< 0.15% I
Nenn
Nenn
< 9.2 mA
< 4.1 mA
PP
PP
≤ 0.2% I
≤ 0.2% I
Nom
Nom
0...3060 W
0...3060 W
< 1% P
< 1% P
Nenn
Nenn
< 0.05% P
< 0.05% P
Nenn
< 0.75% P
< 0.75% P
Nenn
~ 94%
~ 95%
~ 92%
~ 94%