Connections
For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.
Use 12-28 AWG Cu Wire rated for temperatures above 70 °C Only,
tighten to . lb-In. Strip wires to 7 mm from the ends. Use a suitable
ferrule for multi-stranded wires (do not solder).
Terminal
Signal
1
24 V DC (out)
2
Current +
3
Common −
4
Voltage +
5
Not used
6
7
Link to change the set-up
8
9
Neutral (−)
10
Live (+)
11
Normally Closed
12
Common
13
Normally Open
14
Normally Closed
15
Common
16
Normally Open
Case
Earthing is via a stud on lower side of case
Input signals
Security Link
Power supply
Alarm Channel One
Alarm Channel Two
17