12.1 EtherNet/IP-Objektklassen
Instance-Attribut (Instance 1..2)
Attribut
Name
1
Interface Speed
2
Interface Flags
3
Physical Address
4
Interface
Counters
5
Media Counters
6
Interface Control
100
Zugang
Datentyp
Get
UDINT
Get
DWORD
Get
ARRAY
Get
STRUCT
Get
STRUCT
Get, Set
STRUCT
12 CIP-Objektklassen
Beschreibung
Current Interface speed in Mbps
Interface Flags:
b0: Link Status
b1: Half (0) or Full (1) Duplex
b2..4: Negotiation Status:
0 = Auto-negotiation in progress
1 = Auto-negotiation and speed
detection failed (using default 10Mbps
and half duplex)
2 = Auto negotiation failed but
detected speed (using default half
duplex)
3 = Successfully negotiated speed
and duplex
4 = Auto-negotiation not attempted
(forced speed and duplex)
b5: Manual Setting Requires Reset
b6: Local Hardware Fault
b7..31: Reserved (0)
MAC address
Interface Counters
Media-specific counters
Configuration for physical interface
Control Bits (WORD):
b0: Auto-negotiate
b1: Forced Duplex Mode (0 = Half
Duplex; 1 = Full Duplex, only valid
when Auto-negotiate = 0)
b2..15: Reserved (0)
Forced Interface Speed in Mbps
(UINT)