48/52
Bosch Rexroth AG
Features
When the respective input signal is detected, the corresponding counters will be
reset, the status outputs will be updated and an echo will be output. These
routines will be only be served if the changes in the respective inputs occur in the
sequence-free time (prior to start or after reset of weld complete) of the timer.
7.1.12 Status/monitorig result
When an error message is detected, it is output as status number at the outputs
7.00 through 7.11. 0 means no message.
0 means no message.
If set point and actual values are part of this message, the percentage deviation
of the actual value from the set point value is output through the outputs
„Deviation (Bit0)" through "Deviation (Bit7)". In case of deviations greater than
127%, the figure 127% will be output.
R911330645 | PSI 6xCx.751