13.1 Connection/wiring diagram
13.1.1 On/Off actuator with relay (code 00), 24 V DC (code C1)
13.1.1.1 Position of the connectors
X1
X2
Actuator version 2070
13.1.1.2 Electrical connection
3
1
2
Plug assignment X1
Pin
L1 / Uv+, direction of travel CLOSED
1
L1 / Uv+, direction of travel OPEN
2
N / Uv-, neutral conductor
3
PE, protective earth conductor
N / L- signals in the unit are separated.
The potential must be assigned by the user.
When the OPEN and CLOSED switches are operated simultaneously the actuator "CLOSES".
13.1.1.3 Connection diagram
Motor protection switch
recommended
L1/Uv+
External wiring
N/Uv-
PE
Connection assignment X1
13.1.2 On/Off actuator with 2 additional potential-free limit switches, with relay (code 0E), 24 V DC (code C1)
13.1.2.1 Position of the connectors
X1
X2
Actuator version 2070
www.gemu-group.com
Actuator version 4100, 4200
Description
Direction
switch
CLOSED
OPEN
1
3
2
Actuator version 4100, 4200
X1
X2
X1
X2
117 / 136
13 GEMÜ 9468 electrical connection
X1
X2
X2
X1
GEMÜ R488 Victoria

Kapitel