Ventilation Mode - Helios AIR1 XH Serie Montage- Und Betriebsvorschrift

Zentral-lüftungsgeräte
Inhaltsverzeichnis

Werbung

Installation and Operating Instructions
EN
+
NOTE
+
NOTE
Central ventilation units AIR1 XH
Outdoor comp setp
10.0 °C = 18.0 °C
15.0 °C = 18.0 °C
2�4�7 Ventilation mode
The ventilation mode is set during commissioning. This setting can be modified later using the commissioning
assistant (operating level Admin) only.
The following ventilation modes are available:
• Constant volume flow
• Constant speed
• Constant pressure
• External fan control
If "External fan control 0-10 V" is selected using the commissioning assistant (wizard), the other modes will not be
available.

Ventilation mode

Constant volume flow
The ventilation mode is used to select the different fan control variants. Press the
menu to select the ventilation mode. Press the
supply air and extract air fans are set for three ventilation stages (reduced, normal, boost) in m³/h in the constant
volume flow mode or in % in the constant speed mode. In the constant pressure mode, the duct pressure is set in
Pa. Press the
button to adjust and press the
The following functions can be selected for the ventilation mode:
• Constant volume flow (m³/h)
• Constant speed (%)
• Constant pressure (Pa)
a� Constant volume flow
3 ventilation stages are available:
• Reduced
• Normal
• Boost
Each ventilation stage has two independent settings for the supply and extract air fan.
When "Constant volume flow" is selected, the volume flows can be set in the "fan control" menu separately for the
supply air fan and the extract air fan:
SAF CVF setp.
Reduced: XXX m³/h
Normal: XXX m³/h
Boost: XXX m³/h
EAF CVF setp.
Reduced: XXX m³/h
Normal: XXX m³/h
Boost: XXX m³/h
When setting the ventilation stage „minimal", please observe the minimum volume flow� For minimum flow
see table „Technical data", chapter 3�0�
b� Constant speed
3 ventilation stages are available:
• Reduced
• Normal
• Boost
Each ventilation stage has two independent settings for the supply and extract air fan.
When "Constant speed" is selected, the volume flows can be set in the "fan control" menu separately for the supply
air fan and the extract air fan.
SAF Const. speed setp.
Reduced: XXX %
Normal: XXX %
Boost: XXX %
OK
OK
OK
OK
button to set the ventilation mode. The air volume flows of the
button to confirm.
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
41
OK
OK
OK
OK
OK
OK
button in the "ventilation mode"
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis