Helios AIR1 XH Serie Montage- Und Betriebsvorschrift Seite 139

Zentral-lüftungsgeräte
Inhaltsverzeichnis

Werbung

Installation and Operating Instructions
The submenus of the main menu (Part 2 of 2)
7. Inputs / Outputs
AI
AI1: 0.0 Inactive
AI exp3
AI2: 45.5 Humidity
AI exp4
AI3: 0.0 Inactive
DI
AI4: 0.0 Inactive
UI
Each with arrow to the right
UI exp 3
to view signals at
UI exp 4
inputs / outputs.
AO
Each with arrow to the right
DO
to view signals at
inputs / outputs.
8. Manual / Auto
10. Configuration
Supply temp contr
Inputs / Outputs
Auto
Sensor settings
Manual setting: 100.0
Control function
Fan control
Extra sequenc e Y4
SAF: Auto
Extra sequence Y5
Manual set: 100.0
Heating
Exchanger
Cooling
EAF: Auto
Pump control
Manual set: 100.0
Free cooling
Support control
Fire function
Exchanger
Smoke detector func
Auto
Exchanger deicing
Manual set: 100.0
Exch frost prevent
P1 heating
Auto
P1 exchanger
Auto
Actuator run time
P1 cooling
Actuator period tim
Auto
Step controllers
Recirculation
Outdoor air damper
Alarm settings
Communication
Auto
Other parameters
System
Exhaust air damper
Auto
Extra sequence Y5
Auto
Manual set: 0.0
Central ventilation units AIR1 XH
9. Settings
Control temp
Control flow
Alarm settings
Restore factory
settings: No
Restore user
settings: No
Save user settings:
No
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Cooling recovery
Use the arrow to the right
Min limit dampers
to go to the submenus.
Run ind/Motor prot
Display on the
Type of actuator
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Use the arrow to the right
to go to the submenus.
Display on the
following pages
Supply air control
P-band: 33.0 °C
I-time: 100.0 s
Frost protection
Flow control SAF
P-band: 21250.0 m3/h
I-time:
60.0 s
Min. output: 0
%
Flow control EAF
P-band: 21250.0 m3/h
I-time:
60.0 s
Min. output: 0
%
Alarm limits
Alarm delays
Restore alarm
Service alarm
(Filter alarm)
Time counter set
to zero: No
60
Frost protection
Active
Setp shutdown: 25.0C
P-band active: 5.0C
Fast stop at frost-
protection alarm: Yes
Sequence with
frost prot
Y1 heating
Al lim supply air
Control dev : 10.0 °C
High temp : 35.0 °C
Low temp: 10.0 °C
Al del supply air
Al lim extract air
Control dev : 30 Min
High temp : 30.0 °C
High temp : 5 s
Low temp : 10.0 °C
Low temp : 5 s
Al del extract air
Control dev
high temp : 30 min
SAF: 50.0 m3/h
Low temp : 30 min
Alarm delay
Control dev
Frost prot: 0 s
EAF: 50.0 m3/h
Frost risk : 0 s
Alarm delay control
Low efficiency
dev pressure
50.0 %
SAF: 30 Min
Service alarm
Alarm delay control
(Filter alarm)
dev pressure
Time until alarm
EAF: 30 Min
activates: 0 months
Alarm limit (X1, Y1)
Low efficiency
filter guard1
30 min
22.0
Pa at
0
m3/h
Alarm limit (X2, Y2)
Alarm delay
filter guard1
malfunction
90
Pa at
SAF: 120 s
4500
m3/h
Alarm limit (X3, Y3)
Alarm delay
filter guard1
malfunction
178.8
EAF: 120 s
10000
Alarm delay malfunc
Alarm limit (X1, Y1)
P1 heating: 5 s
filter guard2
P1 cooling : 5 s
20.0
P1 exchan : 20 s
0
Alarm limit (X2, Y2)
Filter guard1: 180s
Filter guard2: 180s
filter guard2
75
Flow switch : 5 s
Frost prot: 0 s
4500
Alarm delay
Alarm limit (X3, Y3)
Deicing DI: 0 s
filter guard2
Fire alarm : 0 s
165.8
Ext alarm
: 0 s
10000 m3/h
Alarm delay
Elec heat
: 0 s
Sensor error : 15 s
Rot sent exch: 20 s
EN
Pa at
m3/h
Pa at
m3/h
Pa at
m3/h
Pa at