Herunterladen Inhalt Inhalt Diese Seite drucken

Pneumatic Connections; Electrical Connections; Initialisation And Commissioning; Electrical And Pneumatic Connection - Gemü 1434 mPos Original Einbau- Und Montageanleitung

Vorschau ausblenden Andere Handbücher für 1434 mPos:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5

Pneumatic connections

2
1
Connection
Description
1
Air supply connection P (max. 10 bar)
2
Working connection process valve A1
3
Venting connection R
Max. air supply 8/10 bar!
6

Electrical connections

2
X1
3
5
1
4
Connection Pin Signal name
1
U
, 24 V DC supply voltage
V
I+ / U+, 4-20 mA / 0-20 mA / 0-10 V
2
(set value input)
X1
3
I- / U- GND
A coded
I+ / U+, 4-20 mA / 0-20 mA / 0-10 V
4
M12 plug
(actual value output-optional)
U
, initialisation 24 V DC,
V
5
initialisation is started by an impulse
signal t ≥ 1 s
1434 µPos
®
3
2
X3
1
5
3
4
X1
X3
Danger of cable break!
P Damage to the device.
P The electrical connections are fixed.
● Do not turn the electrical connections.
For connection cables >30m
install precautionary measures
against surge voltage!
7
Initialisation and
commissioning
7.1
Electrical and pneumatic
connection
1. Turn on pneumatic air supply
(max. 8/10 bar).
Legend
LED
OFF
ON
X1
Flashes fast
Flashes slow
2. Switch on 24 V DC power supply.
X3
POWER LED on.
LED
OPEN
ERROR
GND
+24V DC
16 / 24
CAUTION
Symbol
m
l
b
I
Symbol
LED
CLOSED
I
POWER
b
4
1
Symbol
I
l
3
5
2

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis