1. Make the connection between pneumatic positioner outlet A1 (single acting) or A1
and A2 (double acting) and the pneumatic actuator air control inlet.
2. Connect the control air supply (additional air) to connector P (max. 6 bar or 90 psi).
Con-
nector
P
R
D1
D2
RV
A1
A2
* only double acting type (code 3)
4
4.1
1. Connect travel sensor (if not already connected).
2. Connect analogue input 0/4-20 mA or 0-10 V for specifying set value to correct terminals.
3. Connect power supply cable 24 V DC and potential - earth.
Damage to the spindle surface may lead to failure of the travel sensor!
Downloaded from
www.Manualslib.com

Pneumatic connections

RV
DIN
ISO
Description
1219-1
1
Air supply connector G1/4
3
Venting connection G1/4 with silencer
V1
Exhaust air throttle for A1
V2
Exhaust air throttle for A2*
V3
Non-return valve
2
Working connection for process valve
4
Working connection for process valve*

Electrical connections

Version with terminals (standard)

manuals search engine
D2
A2
A1
D1
Note
Filter strainers are installed in the
pneumatic connectors of the positioner to
protect against rough dirt particles. They
can be ordered as spare parts with order
number 1435 SFI. Each kit contains 3
filter strainers. These filter strainers are
meant as an additional protection and do
not replace the requirement to filter all site
compressed air.
CAUTION
17 / 24
P
R
1435 ePos
®