Siemens SITRANS FST020 IP65 NEMA 4X Betriebsanleitung Seite 15

Ultraschall-durchflussmessgeräte
Vorschau ausblenden Andere Handbücher für SITRANS FST020 IP65 NEMA 4X:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5. As per local electric codes, wire input power connector P12 for AC or DC power
6. Insert AC or DC power wires into wire entry holes and secure by tightening wire clamp
7. Pull sensor cables through transmitter case cable gland and connect to the appropriate
8. Connect the power cables to the appropriate power source (100-240 VAC @ 50/60 Hz or
FST020 IP65 NEMA 4X Quick Start
Operating Instructions, 08/2014, A5E03086489-AJ
depending on power supply provided.
Connector P12
1
2
3
Note
Dress cables and make sure cable length is not excessive as to impede proper
replacement of access cover.
screws.
Note
Power supply connector wires should be stripped stranded or solid conductors AWG 12 -
18.
UP and DOWN sensor connectors.
11.5-28.5 VDC) and power up unit.
WARNING
Circuit limited to 20 Amps
The branch circuit must be limited to 20A or damage to the unit and personnel injury will
result.
It is recommended that the circuit breaker be located near the transmitter.
DANGER
Shock Hazard
Will cause death or serious personal injury.
Disable power before servicing fuse F1.
AC
L1
L2/N
GND
2.2 Mounting the Transmitter
DC
POS +
NEG -
GND
Connecting
Wire Color
Black
White
Green
13