10.2 Fault messages and maintenance messages

display text
Fault
Filter dirty!
Filter change required
Maintenance re-
Maintenance interval
quired
required
Outdoor air temp.
The sensor is faulty.
sensor
Lead break on outdoor
air temperature sensor.
SUP temp. sensor The sensor is faulty.
Lead break on supply air
temperature sensor.
ETA temp. sensor The sensor is faulty.
Lead break on extract air
temperature sensor.
EHA temp. sensor The sensor is faulty.
Lead break on exhaust
air temperature sensor.
Air flow monitor-
No feedback from supply
ing SUP
air fan. The fan is faulty.
Cable/lead break.
Air flow monitor-
No feedback from ex-
ing ETA
tract air fan. The fan is
faulty. Cable/lead break.
Door open!
The appliance cover is
Condens. level!
not properly closed.
Please check
Fill level of condensate
pan has been reached.
Condensate pump over-
loaded or faulty.
Following units
pLan network connec-
are OFFLINE!
tion between the units
is interrupted. Incorrect
addressing of units and
programming units.
Unit alarm:
Fault in another unit in
the pLan network.
Fire!
The "smoke alarm" input
has responded.
SUP temp. sensor
Faulty sensor on exter-
Exp�Board
nal hydraulic reheating
coil.
SUP frost risk
The supply air tem-
perature has dropped
permanently below 5 °C.
Possible causes are a
faulty exhaust air flap,
a faulty bypass and a
blocked extract air or
exhaust air duct.
Hydr. reheating
The set maximum supply
Limit SUP MAX
air temperature down-
stream of the hydraulic
reheating coil has been
exceeded. The mixing
valve on the reheating
coil or a sensor is faulty.
26
| VRL-C 300/625/870
effect
Remedy
Maintenance
Replace the filters.
information
Reset the filter
runtime.
Maintenance
Maintenance by
information
qualified contrac-
tor recommended
The appliance
Notify your quali-
shuts down.
fied contractor.
The appliance
Notify your quali-
shuts down.
fied contractor.
The appliance
Notify your quali-
shuts down.
fied contractor.
The appliance
Notify your quali-
shuts down.
fied contractor.
The appliance
Notify your quali-
shuts down.
fied contractor.
The appliance
Notify your quali-
shuts down.
fied contractor.
The appliance
Close the appli-
shuts down.
ance cover.
The appliance
Notify your quali-
shuts down.
fied contractor.
Notify your quali-
fied contractor.
Call up the unit
from the master
programming
unit. Display the
message. Notify
your qualified con-
tractor.
The appliance
Leave the building.
shuts down.
If there is no fire,
have the smoke
alarm checked.
The appliance
Notify your quali-
shuts down.
fied contractor.
The appliance
Notify your quali-
shuts down.
fied contractor.
The appliance
Notify your quali-
shuts down.
fied contractor.
display text
Fault
Cool. mod. fault! Fault in the internal
safety chain of the cool-
ing unit. High or low
pressure fault in the re-
frigerant circuit. There is
a leak in the refrigerant
circuit or the air routes
are blocked.
Outdoor temper-
ature <-25 °C.
Shutdown to pro-
tect cooling unit.
hx module fault ;
Communication fault
hxmodule offline ;
between hx module and
check hxmodule
controller. Cable/lead
break. The hx module is
faulty.
hx module
The application limit of
frost risk ; Sys.
the unit has not been
switched off for
reached.
XX min.
Some units have a fault indicator on the supply air side which
illuminates red when there is a fault message or maintenance
message. As a result you are able to detect faults occurring in
units that are operated without a programming unit.
If you cannot remedy the fault, contact your qualified contrac-
tor. Give the number on the type plate to the qualified contractor
(000000-0000-000000). The type plate is located on the control
panel on the side of the appliance.

Guarantee

The guarantee conditions of our German companies do not
apply to appliances acquired outside of Germany. In countries
where our subsidiaries sell our products a guarantee can only
be issued by those subsidiaries. Such guarantee is only grant-
ed if the subsidiary has issued its own terms of guarantee. No
other guarantee will be granted.
We shall not provide any guarantee for appliances acquired in
countries where we have no subsidiary to sell our products.
This will not affect warranties issued by any importers.

Environment and recycling

We would ask you to help protect the environment. After use,
dispose of the various materials in accordance with national
regulations.
effect
Remedy
The appliance
Notify your quali-
shuts down.
fied contractor.
The appliance
Wait until the
shuts down.
outside temper-
ature has risen.
Acknowledge the
fault by pressing
and holding the
"Alarm" button for
2 seconds.
The appliance
Notify your quali-
shuts down.
fied contractor.
The appliance
The unit starts up
shuts down.
again automati-
cally. The warning
message is dis-
played again for
information.