Herunterladen Inhalt Inhalt Diese Seite drucken

Tips And Recommendations - Atlantic ODYSSEE SPLIT V2 Bedienungsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 141
Warnings
Connect the safety unit directly to the cold water inlet.
Usually, the cold water network pressure is below 0.5 MPa - 5 bar. If this is not
the case, provide for a pressure reducer installed at the water inlet downstream
the meter (recommended setting: 0.35 MPa). Never install the device directly at
the water heater.
Hot water
outlet
Dielectric
connection
Phase
Earth
Neutral
Cold water
3.3.

Tips and recommendations

If the taps have not been equipped with thermostatic mixers, install a temperature limiter
at the hot water outlet to reduce the risk of scalding:
For bathrooms, the maximum tap water temperature is 50 °C.
In all other rooms, the maximum tap water temperature is 60 °C.
For regions with water having a high mineral content (Water hardness - Th>20°f),
water treatment is recommended. With a water softener, the hardness of the
water must remain above 8°f. The water softener does not give rise to a waiver
of our warranty, provided that it is approved for France by CSTB and set in ac-
cordance with good engineering practices, checked and maintained regularly.
Directive no. 2001-1220 as from 20 December 2001 and circular DGS/SD 7A.
In compliance with DTU 60.1
18
Presentation
General installation diagram
Example for suspended device
outlet Cold water
inlet
Pressure
reducer
Siphon
Safety unit
Temperature
YES
limiter
Installation
000 0000
Water meter
General cold
water tap
Water supply
from the network
Wastewater
drain (sewer
system)
Cold water
supply
from the
network
Water supply
from the
network
NO

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis