2.
After piping work is finished, check if drainage flows
smoothly.
Open the water inlet lid, add approximately 2 l of water
gradually and check the drainage flow.
Method of adding water. See figure 13.
1
Drain pipe
2
Service drain outlet with rubber plug. Use this outlet to drain
water from the drain pan.
3
Plastic container for pouring
Drain piping connections
Do not connect the drain piping directly to sewage
pipes that smell of ammonia. The ammonia in the
sewage might enter the indoor unit through the drain
pipes and corrode the heat exchanger.
Keep in mind that it will become the cause of getting
drain pipe blocked if water collects on drain pipe.
When electric wiring work is finished
Check drainage flow during COOL running, explained in the chapter
"Test operation" on page 8.
When electric wiring work is not finished
Remove the switch box lid and connect the power supply and
remote controller to the terminals.
See figure 22.
1
Switch box lid
2
Remove the switch box lid (take off 2 screws)
3
Power supply terminal block
4
Remote controller terminal block
5
Remote controller wiring
Next, press the inspection/test operation button
remote controller. The unit will engage the test operation
mode. Press the operation mode selector button
selecting fan operation
. The indoor unit fan and drain pump will start up. Check
that the water has drained from the unit. Press
back to the first mode.
Note that the fan also starts rotating.
Attach the switch box lid as before.
E
LECTRIC WIRING WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.
Use copper wire only.
Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".
All wiring must be performed by an authorized electrician.
A circuit breaker capable of shutting down power supply to the
entire system must be installed.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.
Installation and operation manual
5
Downloaded from
www.Manualslib.com
TEST
. Then, press the on/off button
manuals search engine
This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal board wiring to
the outdoor unit and HR box are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.
Refer to the installation manual attached to the outdoor unit for
the size of power supply electric wire connected to the outdoor
unit, the capacity of the circuit breaker and switch, and wiring
instructions.
Be sure to ground the air conditioner.
Do not connect the ground wire to gas pipes, water pipes,
lightning rods, or telephone ground wires.
Gas pipes: might cause explosions or fire if gas leaks.
Water pipes: no grounding effect if hard vinyl piping is used.
Telephone ground wires or lightning rods: might cause
abnormally high electric potential in the ground during lightning
storms.

Electrical characteristics

Model
Hz
S-20YM3HPQ
S-25YM3HPQ
S-32YM3HPQ
50
S-40YM3HPQ
S-50YM3HPQ
MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
kW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)
NOTE
For details, refer to "Electrical data".
on the
until
Specifications for field supplied fuses and wire
to go
TEST
Field
Model
fuses
S-20YM3HPQ
S-25YM3HPQ
S-32YM3HPQ
15 A
S-40YM3HPQ
S-50YM3HPQ
NOTE
For details, refer to the chapter "Wiring example"
on page 7.
Allowable length of transmission wiring between
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:
Power
Units
supply
Voltage
Volts
range
MCA
MFA
0.8
15
0.8
15
≤264
220-240
0.8
15
≥198
0.8
15
0.9
15
Remote controller wiring
Power supply wiring
and Transmission wiring
Size,
Wire
length
Wire
Wire size
and length
Sheathed
must
H05VV-U3G
wire
comply with
(2 wire)
local
codes.
Outdoor unit - indoor unit: ≤1000 m
(total wiring length: 2000 m)
Indoor unit - remote controller: ≤500 m
Urban Multi air conditioner
Fan motor
kW
FLA
0.055
0.6
0.055
0.6
0.055
0.6
0.055
0.6
0.055
0.7
Size
2
0.75~1.25 mm
S-20~50YM3HPQ
4PW18607-1A