Herunterladen Inhalt Inhalt Diese Seite drucken

Gemü 566 Betriebsanleitung Seite 95

Vorschau ausblenden Andere Handbücher für 566:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

12.4.29 Operating times
The current valve travel times can be read out with the Operating times parameter.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x62
1
0
RO
2
8
RO
Description of parameter values
Index name
Operating times
12.4.30 Drive sets
The force of the actuator can be influenced with the Drive sets parameter when the valve is initialized and during initialization.
In-
Sub
Off-
Access
dex
-
set
Rights
In-
dex
0x90
2
8
R/W
3
16
R/W
Description of parameter values
Index name
Drive sets
Force settings
Actuator size
AG0 and AG1
www.gemu-group.com
Lengt
Index name
h
Operating times
8 bits
8 bits
Parameter
Open
0 to 25.5 s
Close
0 to 25.5 s
Lengt
Index name
h
Drive sets
3 bits
3 bits
Parameter
Force
Force initialization
Parameter
Open
Close
Values
0 to 255
Read out operating time (in tenths of seconds) from end
position CLOSED to end position OPEN.
0 to 255
Read out operating time (in tenths of seconds) from end
position OPEN to end position CLOSED.
Parameter
Force
Force initializa-
tion
Values
1 ... 6
Set the force of the valve. Preset at the factory depending on
the valve type.
1 ... 6
Set the force during initialization. Preset at the factory
depending on the valve type.
Setting parameter
1
6
95 / 112
12 Specific data IO-Link (pin 6)
Type
Default
uint:8
0
uint:8
0
Description
Type
Default
uint:16
-
uint:16
-
Description
Force
Minimum force
Maximum force
Values
0 to 255,
0 to 25.5 s
0 to 255,
0 to 25.5 s
Values
1 ... 6
1 ... 6
GEMÜ 566

Werbung

Kapitel

Inhaltsverzeichnis
loading