Herunterladen Inhalt Inhalt Diese Seite drucken

Pumped Liquids; Technical Data - DAB Evoplus Small Serie Installationsanweisung Und Wartung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 88
GB
ENGLISH

3. PUMPED LIQUIDS

The machine has been designed and made for pumping water, free from
explosive substances and solid particles or fibres, with a density of 1000
Kg/m³, a kinematic viscosity of 1mm²/s and non chemically aggressive
liquids. It is possible to use ethylene glycol in a percentage of no more
than 30%.
4. APPLICATIONS
EVOPLUS SMALL series circulators allow integrated adjustment of
the differential pressure which enables the circulator performance to be
adapted to the actual requirements of the system. This determines con-
siderable energy saving, a greater possibility of control of the system,
and reduced noise.
EVOPLUS SMALL circulators are designed for the circulation of:
- water in heating and conditioning systems.
- water in industrial water circuits.
- domestic water only for the versions with bronze pump body.
EVOPLUS SMALL circulators are self-protected against:
- Overloads
- Lack of phase
- Excess temperature
- Over-voltage and under-voltage
16
Downloaded from
www.Manualslib.com
manuals search engine

5. TECHNICAL DATA

Supply voltage
Absorbed power
Maximum current
Grade of protection
Protection class
TF Class
Motor protector
Maximum environment temperature
Liquid temperature
Flow rate
Head
Maximum working pressure
Minimum working pressure
Lpa [dB(A)]
1x220-240 V (+/-10%), 50/60 Hz
See electrical data plate
See electrical data plate
IP44
F
TF 110
No external motor protector is
needed
40 ºC
-10 ºC ÷ 110 ºC
See Table 1
See Table 1
1.6 MPa
0.1 MPa
<= 33

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis