3. Specifications
Thermometer with transmitter and output signal 4 ... 20 mA
(model TR31-x-x-TT)
Influence of the ambient
temperature
Electromagnetic
compatibility (EMC)
Temperature units
Info data
Configuration and
calibration data
Electrical connection
Readings in % refer to the measuring span
For a correct determination of the overall measuring deviation, both sensor and transmitter
measuring deviations have to be considered.
1) The temperature transmitter should therefore be protected from temperatures over 85 °C (185 °F).
2) Version with mineral-insulated sheathed cable can be used up to 300 °C (572 °F).
3) ±0.2 % for measuring ranges with a lower limit less than 0 °C (32 °F)
4) Use resistance thermometers with shielded cable and ground the shield at at least one end
of the lead if the lines are longer than 30 m or leave the building. Operate the instrument in a
grounded state.
5) During transient interferences (e.g. burst, surge, ESD) take into account an increased measuring
deviation of up to 2 %.
WIKA operating instructions models TR31-3, TR31-K
Downloaded from
www.Manualslib.com
5)
manuals search engine
0,1 % of the span / 10 K T
EN 61326 emission (group 1, class B) and
interference immunity (industrial application)
configuration at 20 % of the full measuring range
Configurable °C, °F, K
TAG No., descriptor and user message can be
stored in transmitter
Permanently stored
M12 x 1 circular connector (4-pin)
Directly connected cable
a
4)
EN
,
11