14.5 separateD vertICal flue termInals InstallatIon optIons
L max = 14 m
L max = 15 m
Important: if fitting a single exhaust flue duct, ensure it is adequately insulated (e.g.: with glass wool) wherever the duct
passes through building walls.
For detailed instructions concerning the installation of fittings refer to the technical data accompanying the fittings.

15. ConneCtIng the maIns supply

Electrical safety of the appliance is only guaranteed by correct grounding, in compliance with the applicable laws and
regulations.
Connect the boiler to a 230V monophase + ground power supply by means of the three-pin cable supplied with it and
make sure you connect polarities correctly.
use a double-pole switch with a contact separation of at least 3mm in both poles.
In case you replace the power supply cable fit a HAR H05 VV-F' 3x0.75mm
cable with an 8mm diameter max.
2
The fuse, a fast-acting type rated 2A, is incorporated into the power supply terminals (remove the black fuse holder to
enable inspection and/or replacement.)
terminals M1
terminals M2
cover
cover
Figure 11
cautIon
If the appliance is directly connected to a underfloor system, install a safety thermostat to prevent the latter from overheating.
InstructIons pertaInInG to the InstaLLer
926.423.1 - GB
48