SAFETY RIBBONS - REMARKS
If several edges, with normally closed contacts, are used, the
outputs should be connected in series.
If several conductive rubber edges are used, the outputs
should be connected in cascade, and only the final edge
should be terminated on the nominal resistance.
Active edges connected to the accessory power supply are
inactive when the control unit switches to ENERGY SAVING
mode.
To meet the requirements of EN12978, it is necessary to
install conductive rubber sensitive edges; contact normally
closed sensitive edges should have a control unit that
constantly verifies their correct operation. If control units
with the option to conduct testing by interrupting the power
are used, connect the control unit power cables between
terminals E3 (+) and
E2 (-) on the PD13.
Otherwise, connect them between terminals E1 (+) and E2 (-).
Testing the edges should be activated by means of the
menu.

4.6 - CONNECTING SAFETY RIBBONS

The control unit considers two kinds of safety ribbons, depending
on the terminal to which they are connected:
Type 1 (fixed)
They are mounted on walls or on other fixed obstacles that are
approached by the gate doors during the opening phase.
When type 1 safety ribbons operate during the gate opening
phase, the control unit will close the doors for 3 seconds, then it
stands still; when type 1 safety ribbons operate during the gate
closing phase, the control unit will stand still immediately. The
direction of the gate at next command of START or PEDESTRIAN
START depends upon the parameter STOP (it inverts or continues
the motion).
If the input STOP is disabled, the command makes the motion
continue in the same direction.
Type 2 (mobile)
They are mounted to the door ends.
When type 2 safety ribbons operate during the gate opening
phase, the control unit will stand still immediately; when type 2
safety ribbons operate during the gate closing, the control unit
will open the doors for 3 seconds, then it will stand still. The
direction of the gate at next command of START or PEDESTRIAN
START depends upon the parameter STOP (it inverts or continues
the motion).
If the input STOP is disabled, the command makes the motion
continue in the same direction.
Both the input can manage the classic safety edge with n.c.
contact and the conductive rubber safety edge with 8,2
kohm nominal resistance.
Connect type 1 safety ribbons cables between terminals
J7 (EDGE1) and J9 (COM) of the control unit.
Connect type 2 safety ribbons cables between terminals
J8 (EDGE2) and J9 (COM) of the control unit.

4.7 - LOW VOLTAGE LIGHT OUTPUT

The PD13 control unit has a 24 VDC output that allows
connection of a maximum load of 3W.
This output can be used to connect a warning light, indicating the
status of the gate, or for a low voltage flashing light.
Connect the low voltage signal light or flashing light wires to
terminals E4 (+) and E5 (-).
CAUTION: Pay attention to the polarity of the connected
device if necessary.

4.8 - COURTESY LIGHTS

Thanks to the output COURTESY LIGHT the control unit allows
the connection of an electric appliance (e.g. courtesy light or
Ed.tE
garden lights), controlled automatically or by means of the special
transmitter key.
The courtesy light terminals can be alternatively used for a
230V/120V flashing light with integrated flasher.
The output COURTESY LIGHT is a simple N.O. contact with no
power supply.
Connect the cables to terminals B1 and B2.

4.9 - EXTERNAL AERIAL

We suggest to use the external aerial (model: ANS433) in order to
guarantee the maximal range.
Connect the antenna hot pole to terminal A2 (ANT) of the
control unit and the shield to terminal A1 (ANT-).

4.10 - PLUG IN RECEIVER

PD13 control unit is suitable for plugging in a MR receiver having
a high-sensitivity super-heterodyne architecture.
m
WARNING: Pay attention to the way you connect the
removable modules.
MR module receiver is provided with 4 channels and each of
them is suitable for a command of PD13 control unit:
CHANNEL 1
CHANNEL 2
CHANNEL 3
CHANNEL 4
NOTE: Before programming 4 channels and function logics
read carefully the instructions of MR.
- 37 -
g
START
g
PEDESTRIAN START
g
STOP
g
COURTESY LIGHT