6.5.2
Concentric exhaust duct
=
395
There are two types of connector for concentric exhaust ducts, (A) and (B). The vertical duct (A) permits the insertion of a vertical
concentric exhaust duct or a concentric curve at 90° or 45° for connecting the boiler to the flue and air ducts in any direction as it
can be turned by 360°. The connector (B) is a concentric curve at 90° designed for installations where there is limited space at the
top between the boiler and the wall flue outlet.
If fumes are discharged outside the building, the flue-air duct must protrude at least 18 mm from the wall to allow a weathering
surround to be fitted and sealed to avoid water infiltrations.
Secure the intake pipes with two galvanised screws with a diameter of 4.2
mm and a maximum length of 16 mm.
Before securing the screws, make sure that at least 45 mm of the pipe is
inserted into the gasket.
Make sure there is a minimum downward slope of 5 cm per metre of duct
towards the boiler.
INSTALLING THE CONCENTRIC EXHAUST CONNECTOR
Position the connector as shown in the figure and turn it clockwise to secure it on the boiler.