Herunterladen Inhalt Inhalt Diese Seite drucken

General Information; Operating Conditions - Salda SAV 2000 Montage-Und Installationsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 18
SYMBOLS AND MARKING
1 - Logo; 2 - Product code (SKU); 3 - Product name; 4 - Technical data; 5 - Lot number and production date; 6 - Production place.

GENERAL INFORMATION

• Before installing the unit read the entire information provided in this document.
• Installation of the unit shall only be performed by trained and qualified personnel aware of installation of such type of units, inspection, mainte-
nance and tools required for installation works.
• While installing the unit, observe the international and national mechanical and electrotechnical safety requirements of the country in which the
product is intended to be installed and used.
• If the provided information is unclear or any doubts arise regarding safe installation and operation, please contact the manufacturer or repre-
sentative.
• The unit shall be operated only under the below listed conditions.
• It is strictly forbidden to use the unit for non-designed purposes or in contradiction to the specified working conditions without written permission
of manufacturer or representative.
• The manufacturer or representative shall be notified about any fault, including description of the fault and data specified on the product's label.
• Any repair or dismantle of the unit in case of fault is forbidden without previous written permission of manufacturer or representative.
• Dismantling, repair or modification of the unit shall be performed only upon previous written consent from manufacturer or representative.
• The end user shall ensure that the unit is suitable for environmental conditions before ordering and installing the unit.
TRANSPORTATION AND STORAGE
All units are packed in the factory to withstand regular conditions of transportation.
Upon unpacking, check the unit for any damages caused during transportation. It is forbidden to install damaged units!!!
The package is only a protection means!
At unloading and storing the units, use suitable lifting equipment to avoid damages and injuries. Do not lift units by holding on power supply ca-
bles, connection boxes, air intake or discharge flanges. Avoid hits and shock overloads. Before installation units shall be stored in a dry room with
the relative air humidity not exceeding 70% (at +20°C) and with the average ambient temperature ranging between 0°C and +30°C. The place of
storage shall be protected against dirt and water.
The storage is not recommended for a period longer than one year. In case of storage longer than one year, it is necessary to check free rotation
of bearings before installation (turn the impeller by hand).
DESCRIPTION
Casing is made of galvanized sheet and is coated with powder paint RAL 7040.
Water heater.
Efficient and silent fan.
Motor is controlled using voltage.
Grilles on the unit allows to change the direction of the supply air.
PURPOSE OF THE DEVICE
Unit is designed for room air heating and is designed to supply only clean air (free of chemical compounds causing metal corrosion, of substances
aggressive to zinc, plastic and rubber, of fats and of particles of solid, adhesive and fibred materials).

OPERATING CONDITIONS

Unit is designed for indoor use only in temperature between 0°C and +40°C and relative humidity must not exceed 70%.
If operated in temperatures bellow 0°C, the antifrost protection of the water heater must be ensured.
Units are forbidden to be used in potentially explosive environment.
Unit is designed to supply only clean air (free of chemical compounds causing metal corrosion, of substances aggressive to zinc, plastic and rub-
ber, of fats and of particles of solid, adhesive and fibred materials) to a room.
Maximum water temperature 100°C.
Maximum water pressure 1.6 Mpa.
2
| EN
1
3
Product name
AS THE HEAT EXCHANGER IS NOT ENTIRELY
DRAINABLE, MAKE SURE THAT IT IS FILLED WITH
A SUITABLE ANTIFREEZING MIXTURE IN CASE
OFFREEZING RISK.
4
Weight
00,00 kg
6
Made in Šiauliai, Lithuania