6.8 ATEX/IECEx protection

ATEX/IECEx protection can be activated/deactivated by means of DIP switch 10.
ATEX/IECEx protection
Deactivated
Activated

7. Start-up

When the IO 111 has been set up as described in
5. Installation, start-up must be carried out by an
authorised person.
1. Switch on the power supply to the IO 111 before
starting the pump.
2. The IO 111 now carries out a self-test. All
indicator lights on the front panel will be on for a
few seconds. If the IO 111 does not detect any
fault, all indicator lights will go out except those
for water in oil and stator insulation resistance. If
a fault is detected, the indicator light for the
actual fault will illuminate.
3. Check that there are no warnings or alarms
before switching on the pump.
ON
DIP
1 2 3 4 5 6 7 8 9 10
10
10

8. Indication

On the front the IO 111 has ten indicator lights for
sensor status. Figure 9 shows the location of lights
on the IO 111, and the table describes their
indication.
15
13
12
Fig. 9
Description
Activation of ATEX/IECEx protection
enables additional alarms:
• Main bearing temperature to high.
Default alarm temperature: 140 °C
(installation with SM 111)
• Support bearing temperature to high.
Default alarm temperature: 140 °C
(installation with SM 111)
• Missing signal from bearing sensor
(installation with SM 111)
• Missing signal from water-in-oil
sensor
• Communication alarm
(installation with SM 111).
Reset
Indicator lights on the IO 111
6
7
8
15