1. Preliminary Site Survey
Electrical supply and installation is to conform to local
authority's (e.g. National Electrical Board) codes and
regulations.
Voltage supply fluctuation must not exceed ±10% of
the rated voltage. Electricity supply lines must be
independent of welding transformers which can cause
high supply fluctuation.
Ensure that the location is convenient for wiring,
piping and drainage.
Figure A
M
G
F
Model
20
25
A
1214
1214
B
666
666
C
273
273
D
130
130
E
1160
1160
F
27
27
G
77
77
H
745
745
I
25
25
J
209
209
K
486
486
L
108
108
M
360
360
Please ensure that the following steps are taken:
Check the gradient for drainage flow as recommended
in Figure B.
Provide clearance for easy servicing and optimal air flow
as shown in Figure C.
The indoor unit must be installed such that there is no
short circuit of the cool discharge air with the warm
return air.
Do not install the indoor unit where there is direct
sunlight shining on the unit. The location should be
suitable for piping and drainage installation. The unit
must be a large distance away from the door.
3. Semi-Enclose Mounting
In case the unit is to be half recessed into false ceiling, please check the unit is well aligned.
Provide the installation space as shown in Figure D.
Figure D
300mm (min)
10mm

INSTALLATION OF INDOOR UNIT

A
I
H
J
L
E
30
40
50
1214
1714
1714
666
666
666
273
273
273
130
130
130
1160
1560
1560
27
27
27
77
77
77
745
1235
1235
25
25
25
209
331
331
486
486
486
108
108
108
360
600
600
300mm (min)
10mm
Top Panel of Unit
Ceiling Board
10mm
2. Standard Mounting
Ensure that the overhead supports are strong enough to
hold the weight of the unit.
Position the hanger rods (wall mounting bracket for floor
standing), and check for its alignment with the unit.
Also, check that the hangers are secured and the base of
the fan coil unit is leveled in both horizontal directions,
taking into account the gradient for drainage flow as
recommended in Figure B.
Figure B
Figure C
300mm (min)
Ceiling Type
400mm (min)
Floor Standing Type
621mm
10mm
1-3
10mm (min)
Drainage Pipe Side
250mm (max)
Utensils, furnitures
or built-in
architectural features
must not protrude
more than 250mm
1.0m (min)