Herunterladen Inhalt Inhalt Diese Seite drucken

Aurora PVI-3.0-OUTD-S-ZZ Installations- Und Konfigurationsmanual Seite 222

Photovoltaik wechselrichter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 51
APPENDIX
MODEL
INPUT PARAMETERS
Nominal DC Power [kW]
Max. Recommended DC Power [kW]
Operating Input Voltage Range [V]
Full Power MPPT input voltage range (symmetrical load) [V]
Full Power MPPT input voltage range (asymmetrical load) [V]
Absolute Max. Input Voltage [V]
Activation voltage "Vstart" [V]
No of independent MPPT trackers
Max. Input Power, each MPPT [kW]
No. of DC Inputs
Max. DC Current, each MPPT [A]
DC Connection
INPUT PROTECTION
Reverse polarity protection
Fuse rating, each input (-FS suffi x versions only)
DC side varistors
PV array Insulation Control
DC Switch (-S/-FS suffi x versions only)
OUTPUT PARAMETERS
Nominal AC Power [up to 50°C, kW]
Max. AC Power [kW]
AC Grid Connection
Nominal AC Voltage [V]
Maximum AC Voltage Range [V]
Nominal AC Frequency [Hz]
Max. AC Line Current [A]
AC Connection
Line Power Factor
AC Current Distortion [THD%]
OUTPUT PROTECTION
AC side varistors
Ground fault protection (AC + DC leakage current)
ENVIRONMENTAL PARAMETERS
Cooling
Ambient Temp. Range [°C]
Opertaing Altitude [m]
Acoustical Noise [dBA]
Environmental IP Rating
Relative Humidity
MECHANICAL
BOX Dimensions [H x W x D]
Overall Dimensions (whit fl anges) [H x W x D]
Weight [kg]
PVI-10.0-OUTD
10,3
11,4
0,7xVstart - 850 (580 nominal)
300-750
360-750 (@ 6,5kW) / 216-750 (@ 3,9kW)
360 nominal (adjustable within the range 250Vdc-500Vdc, independently/each input)
6,5
6 (3 each MPPT, optionally fused) in PVI-10.0/12.5-OUTD
and in PVI-10.0/12.5-OUTD-FS version
4 (2 each MPPT) in PVI-10.0/12.5-OUTD-S version
12 x MultiContact Ø 4mm (6 male - positive input + 6 female - negative input)
in PVI-10.0/12.5-OUTD and in PVI-10.0/12.5-OUTD-FS version
8 x MultiContact Ø 4mm (4 male - positive input + 4 female - negative input)
in PVI-10.0/12.5-OUTD-S version
Mating cable connector included
Conductor cross section: 4-6mmq/AWG12-10 - Cable Ø w/insulator: 3-6mm
4 ( 2 for each MPPT ), thermally protected
according to VDE0126-1-1
Integrated (Rating: 1000Vdc / 25Adc)
10
11
3 phase 400Vac 50Hz with or without neutral (3 or 4 wires network) + PE
311-456Vac (may be limited in acc. to country-specifi c requirements)
16,6A per phase (19A short circuit)
Screw terminal block
Conductor Cross Section: Solid: 0,5-16mmq / Stranded: 0,5-10mmq / AWG20-6
Cable Gland: M40 - Cable Ø: 19-28mm
<2% at rated power with sine wave voltage
3, star connected to common point, plus gas arrester to ground
according to VDE0126-1-1
-20 / +60 (output power derating above 50°C)
0-100% condensing
PVI-12.5-OUTD
12,8
14,3
360-750
445-750 (@ 8kW) / 278-750 (@ 5kW)
900
2
8
18 (22 shortcircuit)
Yes
10Adc / 900Vdc
12,5
13,8
3x400Vac
50
20A per phase (22A short circuit)
1
Natural cooling
2000
<50 @1mt
IP65
645 x 645 x 211
716 x 645 x 224
38

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis