Hold down for a few seconds the central key "OK", which
will be highlighted -
chosen.
Press the central key to move on to page 11.0.
Pressing the central key + the hidden key takes you
back to the previous page.
Page 11.0:
Page 11.0 shows the alarm history.
Press the central key to move on to page 12.0.
Pressing the central key + the hidden key takes you
back to the previous page
Page 12.0:
With page 12.0 you can set the output relay operating
mode (accessible through terminals 7 and 8).
x
ALARM: The relay closes contacts 7 and 8 if
there is an alarm in the system and opens them
if there is no alarm.
x
PUMP ON/OFF: The relay closes contacts 7 and
8 if the pump is OFF and opens them if the
pump is ON.
Press the central key to move on to page 13.0.
Pressing the central key + the hidden key takes you
back to the previous page
- , to confirm the regulation
.
.
ENGLISH
Page 13.0:
On page 13.0, press the left and right keys to set the
circulator in ON or OFF status, or controlled by a remote
signal EXT.
Hold down for a few seconds the central key "OK", which
will be highlighted -
chosen.
Press the central key to return to the Home Page.
49