Herunterladen Inhalt Inhalt Diese Seite drucken

Regulation With Constant Curve; Regulation With Constant And - DAB BPH-E Serie Installations- Und Wartungsanleitungen

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 58

9.4 Regulation with constant curve.

This is set by means of the control panel on the
cover of the Dialogue or by means of the analog
input 0-10V (ref. terminals 5-6).
The
circulator
works
uncontrolled
circulator,
curves.
Its rotating speed is kept at a constant number of
revs, between n
(840) and n
min
H
Min.
This type of regulation is particularly indicated when
replacing
circulators
systems.
like
a
conventional
on
constant
standard
(2820).
max
Max.
(2820)
Q
(840)
already
existing
ENGLISH
9.5 Regulation with constant and proportional
differential pressure depending on the water
temperature
This is set by means of the control panel on the cover
of the Dialogue
The set point for the head of the circulator is reduced
or increased depending on the water temperature.
The temperature of the liquid may be set at 80°C or
at 50°C.
H
H set.
in
the
This type of regulation is particularly indicated:

in systems with a variable flow rate (two-pipe
heating systems), where a further reduction of the
circulator performance is ensured depending on
the lowering of the temperature of the circulating
liquid, when there is a lower demand for heating.

In systems with a constant flow rate (systems with
single-pipe and underfloor heating), where the
performance of the circulator can be regulated
only with the function influenced by temperature.
42
.
H
20°C 50/80°C
T. (°C)
Q

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis