8. Main parameters

EN
Contents
Set acceleration/ deceleration
time to suit the machinery.
The acc/dec value is time that
output frequency reach from 0Hz
to fh value.
Set the upper and lower limit of the
output frequency
Select the V/f control mode to suit
the machine
Adjust the electronic thermal for
the motor protection.
*1: Default setting values vary depending on the setup menu setting.

9. Panel operation

Status monitor mode





10. Refer to the instruction manual for applied operation or malfunction.
Title
acc
dec
fh
ul
ll
pt
thr
Panel frequency setting
PRG
RUN
MODE
Standard monitor mode
MON
Basic parameter setting
MODE
⇔

MODE

MODE
Function
Acceleration time 1
Deceleration time 1
Maximum frequency
Upper limit frequency
Lower limit frequency
V/F control mode
selection
Motor
electronic-thermal
protection level 1


MODE
PRG
MODE
■ Setting parameters
(1) Select the parameter. (Turn the setting dial.)
(2) Read the setting value. (Press the center of the
setting dial.)
(3) Change the setting value. (Turn the setting dial.)
(4) Determine the setting value. (Press the center of
the setting dial.)
Extended parameter setting


⇔
8
E6581899
Default
Adjustment range
0.0-3600 (360.0) (s)
0.0-3600 (360.0) (s)
30.0-500.0 (Hz)
0.5-fh (Hz)
0.0-ul (Hz)
0: V/F constant
1: Variable torque
2: Automatic torque
boost control
3: Vector control
4: Energy-saving
5: Dynamic energy-
saving
6: PM motor control
7: V/F 5-point setting
10-100 (%/(A))
Setting monitor mode
Search and set
parameters
setting
10.0
10.0
80.0
*1
0.0
*1
100