Screw size
Tightening torque
M3.5 screw
1.0 N·m
M4 screw
1.4 N·m
M5 screw
2.4 N·m
M6 screw
4.5 N·m
M4 screw
(grounding
1.4 N·m
terminal)
M5 screw
(grounding
2.8 N·m
terminal)
5. Turn on the power supply
Set the setup menu after power on.
Caution
Setting dial
Parameter setting
Main region
Motor
Note) When you operare the inverter with external signals, please select Sink logic, Source logic, or
PLC(external power supply) by SW1.
6. Operate the inverter
Panel operation is possible with default settings.
Frequency (speed)
can be changed
with the dial.
8.9 lb·in
Voltage
class
12.4 lb·in
20.8 lb·in
40.0 lb·in
3-phase
12.4 lb·in
240V
24.8 lb·in
1-phase
240V
3-phase
500V
Note 1) The power circuit wire length is assumed to be 30m or less.
If incorrect setting, the drive may has some damage or unexpected
movement. Be sure to set the setup menu correctly.
LED display
"set"
eu
asia
usa
init
0.0
eu
Europe
Asia, Oceania
230/400(V)
230/400(V)
50(Hz)
Wire size (mm
Power circuit Note 1)
Applicable
motor
Input
(kW)
without
With
DCL
DCL
0.4-1.5
1.5
1.5
2.2
2.5
1.5
4.0
4.0
2.5
5.5
10
4.0
7.5
16
6.0
11
25
15
35
0.2-0.75
1.5
1.5
1.5
2.5
2.5
2.2
4.0
4.0
0.4-2.2
1.5
1.5
4.0
2.5
1.5
5.5
4.0
1.5
7.5
6.0
2.5
11
10
4.0
15
16
6.0
Power on
jp
Turn the setting dial and select region.
Press the setting dial
Finish initial setup
asia
usa
North America
230/460(V)
50(Hz)
60(Hz)
Starts with RUN key, and
stops with STOP key.
6
E6581899
)
2
Grounding
cable
Output
1.5
2.5
1.5
2.5
2.5
4.0
6.0
10
10
16
10
16
16
16
25
16
1.5
2.5
1.5
2.5
1.5
4.0
1.5
2.5
1.5
2.5
2.5
4.0
2.5
6.0
6.0
10
10
16
Operation
jp
Japan
200/400(V)
60(Hz)

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis