ELECTRIC WIRING

DSW5: Transmission Setting of End Terminal
Resistance
Factory setting
Cancellation
In the case that the outdoor units quantity in the same H-LINK
is 2 or more, set No. 1 pin of DSW5 at "OFF" side from the 2nd
refrigerant group outdoor unit. If only one outdoor unit is used,
no setting is required.

DSW4 / RSW1: Refrigerant Cycle No. Setting
Factory setting
(Setting for the ten digit).
10.3 COMMON WIRING
!
C A U T I O N
All the field wiring and electrical components must comply with local
codes.
10.3.1 Electrical wiring between indoor unit
and outdoor unit
Connect the electrical wires between the indoor unit and the
outdoor unit, as shown below.
Follow local codes and regulations when performing
electrical wiring.
If the refrigerant piping and the control wiring are connected
to the units in the same refrigerant cycle.
Use twist pair wire (more than 0.75 mm²) for operation wiring
between outdoor unit and indoor unit, and operation wiring
between indoor unit and indoor unit.
Use 2-core wire for the operating line (Do not use wire with
more than 3 cores).
Use shielded wires for intermediate wiring to protect the
units from noise obstacle at length of less than 300 m and
size complied with local code.
Open a hole near the connection hole of power source
wiring when multiple outdoor units are connected from one
power source line.
The recommended breaker sizes are detailed in the Wire
size section.
In the case that a conduit tube for field-wiring is not used, fix
rubber bushes with adhesive on the panel.
All the field wiring and equipment must comply with local and
international codes.
H-LINK twist pair shielded cable must be grounded in the
outdoor unit side.
16
PMML0393B rev.1 - 02/2016

DSW6: Optional function setting
(IVX series only)
For individual operation
(factory setting position)
For IVX series
For simultaneous operation

DSW6: Only for ES series
Factory setting
!
C A U T I O N
Pay attention to the connection of the operating line. Incorrect
connection may cause the failure of PCB.
Check to ensure that the field supplied electrical components
(mains power switches, circuit breakers, wires, connectors and wire
terminals) have been properly selected according to the electrical
data indicated on this chapter and they comply with national and local
codes. If it is necessary, contact with your local authority in regards to
standards, rules, regulations, etc.