Herunterladen Inhalt Inhalt Diese Seite drucken

Hitachi UTOPIA IVX PREMIUM Serie Bedienungsanleitung Seite 22

Serie
Vorschau ausblenden Andere Handbücher für UTOPIA IVX PREMIUM Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 55
REFRIGERANT PIPING & REFRIGERANT CHARGE
8.4 REFRIGERANT CHARGE
!
C A U T I O N
Do not charge OXYGEN, ACETYLENE, or other flammable and
poisonous gases into the refrigerant because an explosion can occur.
It is recommended that oxygen free nitrogen be charged for these
types of tests cycle when performing a leakage test or an airtight test.
These types of gases are extremely dangerous.
Insulate the unions and flare-nuts at the piping connection part
completely.
8.5 CAUTION OF THE PRESSURE BY CHECK JOINT
When the pressure is measured, use the check joint of gas stop
valve (A), and use the check joint of liquid piping (B) in the figure
below.
At that time, connect the pressure gauge according to the
following table because of high pressure side and low pressure
side changes by operation mode.
Check Joint for Gas Stop Valve "A"
Check Joint for Piping "B"
Check Joint for Liquid Stop Valve "C"
8.6 REFRIGERANT CHARGING QUANTITY
Outdoor Units has been charged with refrigerant for 30m of actual piping length. An additional refrigerant charged is required in
systems with actual piping length longer than 30m.
1 Determine an additional refrigerant quantity according to the
following procedure, and charge it into the system.
W
(kg) is the outdoor unit refrigerant charge before shipment explained before, and it's shown in the following table:
0
IVX Premium series
Refrigerant
charge before
Model
shipment
(W
(kg))
0
RAS-3(X)HVNP1E
2.3
RAS-4(X)HVNP1E
4.1
RAS-5(X)HVNP1E
4.2
RAS-6(X)HVNP1E
4.2
RAS-4(X)HNP1E
4.1
RAS-5(X)HNP1E
4.2
RAS-6(X)HNP1E
4.2
RAS-8(X)HNPE
5.7
RAS-10(X)HNPE
6.2
(1) need to be calculate
(*) Only for RAS-H(V)NP(1)E series.
12
PMML0393B rev.1 - 02/2016
Cooling
Heating
Operation
Operation
Low Pressure
High Pressure
High Pressure
Low Pressure
Exclussive for Vacuum Pump
and Refrigerant Charge
Additional
Maximum
refrigerant
additional
charge (P)
charge
(g/m) (*)
(kg)
40
1.2
60
3.9
60
3.9
60
3.9
60
3.9
60
3.9
60
3.9
(1)
10.3
(1)
12.1
Insulate the liquid piping completely to avoid a decrease of
performance; if not, it will cause sweating on the surface of the pipe.
Charge refrigerant correctly. Overcharging or insufficient charging
could cause a compressor failure.
Check for refrigerant leakage in detail. If a large refrigerant leakage
occurred, it would cause difficulty with breathing or harmful gases
would occur if a fire were being used in the room.
If the flare nut is tightened too hard, the flare nut may crack after a
long time and cause refrigerant leakage.
?
N O T E
Be careful that refrigerant and oil do not splash to the electrical parts at
removing the charge hoses.
B
C
A
2 Record the additional refrigerant quantity to facilitate service
activities thereafter.
IVX Standard series
Refrigerant charge
Outdoor unit
before shipment
(W
(kg))
0
RAS-8HNCE
5.7
RAS-10HNCE
6.2
(1) need to be calculate
ES series
Refrigerant charge
Outdoor unit
before shipment
(W
(kg))
0
RAS-4HVRNS3E
2.9
RAS-4HRNS3E
2.9
There may be gas trapped
at the "O-ring screw" part,
which may produce a
sound when released upon
removal of the cap.
However, this is not a gas
leakage.
Additional
Maximum
refrigerant
additional
charge
charge
(g/m)
(kg)
(1)
10.3
(1)
12.1
Additional
Maximum
refrigerant
additional
charge
charge
(g/m)
(kg)
40
1.6
40
1.6

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis