Herunterladen Inhalt Inhalt Diese Seite drucken

Endress+Hauser iTEMP PA TMT184 Bedienungsanleitung Seite 63

Temperaturkopftransmitter
Inhaltsverzeichnis

Werbung

TMT184
Endress+Hauser
Function description
The following table contains all unit matrix functions that are required for the setup of the tempe-
rature head transmitter. Here all functions are listed and described.
Function group: WORKING PARAMETERS
MEASURED TEMP.
• V0H0
TEMP. COMPENSATION
• V0H1
TIME FILTER
• V0H2
RJ MODE
• V0H3
EXT.RJ.VALUE
• V0H4
OFFSET
• V0H5
INPUT 1 CONFIG.
• V2H0
SENSOR TYPE
• V2H1
MEASURING UNIT1
• V2H2
ZERO ENGIN. VALUE
• V2H4
Display of actual measured temperature.
Display of the actually measured internal compensation measurement point tempera-
ture.
Selection of digital filter 1st pass.
Input: 0 to 100 seconds
0 sec.
Selection of internal (Pt100) or external compensation measurement.
Input: undefined; internal; external
internal
!
Note!
Input only possible on selection of thermocouple (TC) sensor type in unit function:
SENSOR TYPE
Input of compensation point measured value.
Input: -40.00 to 85.00 °C (°C, °F, K)
0 °C
!
Note!
Input only possible on selection of thermocouple (TC) sensor type in unit function:
COMPARISON POINT.
Input of zero point correction (Offset).
Input: -10.00 to 10.00 °C (°C, °F, K)
0.00 °C
!
Note!
Value entered will always be reset to default when changing sensor type!
Function group: CALIBRATION
Input of input range
-10 to 75 mV
10 to 400 Ohm
10 to 2000 Ohm
Input of sensor type used or linearisation type.
Sensor type
-10 to 75 mV
LINEAR
Type B, Type C, Type D, Type E, Type J, Type K, Type N,
Type R, Type S, Type T, Type L, Type U
10..400 Ohm
LINEAR
Pt100 DIN/IEC, Pt100 JIS, Ni100
10..2000 Ohm
LINEAR
Pt500, Pt1000, Ni500, Ni1000
Input of engineering units.
Input:
°C, °F, K, Ohm or mV
°C
Start value of sensor measurement range.