24.19
AC-CTR HIGH
LIMIT
0...120%
42 GENER POWER LIMIT
42.05
RESTR ACTPOW
GRD1
0...86400 s
42.06
RESTR ACTPOW
GRD2
0...86400 s
Removed parameters

40 LVRT CONTROL

40.02
NAMU BOARD
ENABLE
OFF
ON
Update notice
FbEq
Description
Defines the maximum reactive power reference value at the AC
controller output. A positive value denotes capacitive reactive
power.
100 =
Maximum reactive power reference value at the AC controller
1%
output
Parameters related to generated active power limiting.
Note: Group 42 is write-protected. It can be write-enabled by
giving a password with parameter 16.03 PASS CODE.
Defines a ramp-up time for active power after the following
network faults:
RT NET LOST
GRID MON FLT
AC UNDERFREQ
AC OVERFREQ
AC UNDERVOLT
AC OVERVOLT
If the ramp-up time defined in parameter
GRD2
is longer than this ramp-up time, it is used instead of this
ramp-up time.
1 = 1 s
Ramp time from zero to 04.06 NOM AC POWER
Defines a ramp-up time for active power after the start-up. This
ramp is used after every start of the inverter.
In addition, if this ramp-up time is longer than the ramp-up time in
parameter
42.05 RESTR ACTPOW
used instead of
occurred.
1 = 1 s
Ramp time from zero to 04.06 NOM AC POWER
Parameters related to the Low voltage ride-through function. Do
not change parameters when the PVS800 is running.
Note: Group 40 is write-protected. It can be write-enabled by giving
a password with parameter 16.03 PASS CODE.
Enables the NAMU grid voltage measuring board. If the signal
01.11 MAINS VOLTAGE is correct or the fault LED on the NAMU
board is not blinking, the communication between the NAMU board
and the inverter control unit is OK. If the communication fails, the
CH2 COM LOST (7520) fault appears.
0
Communication to the NAMU board is disabled.
1
Communication to the NAMU board is enabled.
(32A1)
9.11 SUPPLY FAULT WORD
(8189)
9.10 PV FLT ALM WORD
(3142)
9.01 FAULT WORD 1
(3141)
9.01 FAULT WORD 1
(3120)
9.01 FAULT WORD 1
(3110)
9.01 FAULT WORD 1
42.06 RESTR ACTPOW
GRD1, this ramp-up time is
42.05
after a network fault listed in
Def
100%
0 s
bit 9
bit 0
bit 8
bit 9
bit 10
bit 11
0 s
42.05
has
OFF
T
I
R
R
B