1
Update notice
The notice concerns the following PVS800 central
inverters firmware manuals:
Code
3AUA0000058422
3AUA0000094311
3AUA0000097081
3AUA0000094312
3AUA0000094313
3AUA0000125248
Program features
New (page 38): Active power limitation during grid
underfrequency
In some grid codes and standards it is required that the maximum active output power of the inverter
is increased as the grid frequency decreases. The PVS800 has an adjustable active power limitation
curve based on the measured grid frequency.
The active power limit starts to increase when the grid frequency is below
shown in the figure below. The active power limit cannot decrease while the grid underfrequency
situation is ongoing. As the grid frequency returns to a normal level defined by parameter
PLIM RET
FREQ, the active power limit is ramped down to the level defined by parameter
PLIM LEVEL
1.
Update notice
Rev
Language
C
English
EN
C
German
DE
C
Spanish
ES
C
French
FR
C
Italian
IT
C
Russian
RU
Code: 3AUA0000112613 Rev B
Valid: from 2014-05-13 until the release of Rev D of the
manual. The updates apply to master control program
version GSXR7370 and inverter control program version
ISXR7370.
Contents: This document describes the enhanced functions
of PVS800 central inverters including program feature
descriptions, new parameters and updates for fault and
warning messages.
Modified section has label New, Changed or Deleted
depending on the type of the modification, and a reference to
the page number of the English manual.
46.05 UF PLIM FREQ 1
46.04 UF
46.06 UF
as