13
No.
Name/Value
46.05
UF PLIM FREQ 1
[46.07] ... [46.04]
46.06
UF PLIM LEVEL 1
80% ... [46.08]
46.07
UF PLIM FREQ 2
45 Hz ... [46.05]
46.08
UF PLIM LEVEL 2
[46.06]...120%
Changed parameters
No.
Name/Value
24 REACTIVE POWER
24.04
Q POWER REF
ADD
-120...120%
24.10

LOCK-IN POWER

0...100%
24.11
LOCK-OUT
POWER
0...100%
24.15
AC-CTR GAIN
0...8
24.16
AC-CTR INTEG
TIME
0.1...1000 s
24.18
AC-CTR LOW LIMIT
-120...0%
Update notice
FbEq
Description
Defines the frequency at the first point of the grid underfrequency
characteristic curve.
100 =
Frequency
1 Hz
Defines the active power limit value at the first point of the grid
underfrequency characteristic curve.
1 = 1%
Active power limit in percent of 04.06 NOM AC POWER
Defines the frequency at the second point of the grid
underfrequency characteristic curve.
100 =
Frequency
1 Hz
Defines the active power limit value at the second point of the grid
underfrequency characteristic curve.
1 = 1%
Active power limit in percent of 04.06 NOM AC POWER
FbEq
Description
Reactive power settings
Defines an additional reactive power reference value, which is
added to 24.02 Q POWER REF2.
1 =
Additional reactive power reference in percent of 04.06 NOM AC
1 kVAr
POWER
Defines the lock-in power level for Q(U) control. The active power
has to be greater than this level before the Q(U) control starts
producing non-zero reactive power reference.
100 =
Lock-in value for active power
1%
Defines the lock-out power level for Q(U) control. If the active
power is below this level, the reactive power reference from the
Q(U) control will be zero.
Note: The lock-out power level has to be smaller than the lock-in
power level (24.10 LOCK-IN POWER).
100 =
Lock-out value for active power
1%
Defines the relative gain of the AC voltage controller.
For example, if the gain is set to 1, a 10% change in the error
value (reference - actual value) causes the AC voltage controller
output to change by 10%.
1 = 1
AC voltage controller gain
Defines the integration time of the AC voltage controller.
10 = 1 s
AC voltage controller integration time
Defines the minimum reactive power reference value at the AC
controller output. A negative value denotes inductive reactive
power.
100 =
Minimum reactive power reference value at the AC controller
1%
output
Def
T
49.7 Hz
R
100%
R
49.3 Hz
R
120%
R
Def
T
0 kVAr
R
0%
R
0%
R
2
R
1 s
R
-100%
I