6 EN – Quick installation guide
Step
1
Ground the input cable shields (if present) 360 degrees at the cabinet lead-
through.
2
Connect the twisted shields of the input cables and separate ground cable (if
present) to the cabinet grounding busbar.
3
Step drill carefully sufficiently big holes to the lead-through clear plastic shroud
for the cables to the connected. Align the holes in the vertical direction
according to the alignment holes in the shroud. Smooth the hole edges.
Remove the plastic sheeting from both sides of the shroud.
Attach the cables firmly to the cabinet frame to prevent chafing against the
EN
hole edges.
4
Put the conductors of the input cables through the drilled holes in the clear
plastic shroud.
DA
5
Connect the input power cable conductors to the L1/U1, L2/V1 and L3/W1
connection busbars.
6
Move the lead-through clear plastic shroud along input cables to its final
DE
position. Install the front clear plastic shroud and upper front cover. Remove
the cardboard protective covering from the drive module air outlet.
7
Cut the hole for the lead-through clear plastic shroud in the side clear plastic
ES
shroud. Install the side and top clear plastic shrouds to the drive module.
Install the air baffles
FI
See figure
W
on page
hardware manual.
FR

Connect the control cables

IT
See figure
X
on page 90.
1. Disconnect the control panel cable from connector X13 on the control unit.
NL
2. Loosen the mounting screws of the control panel holder and take the holder off.
3. Install the control cable grounding clamp plate to the control unit.
PL
4. Connect the power supply, BGDR and fiber optic cables to the control unit.
5. Attach the control unit, for example, to a DIN rail.
PT
6. Connect the power supply and BGDR cables to the drive module BPOW and BGDR
terminals. Drive modules with SOIA terminals: Connect the fiber optic cables to the
RU
SOIA terminals.
7. Ground the outer shields of all external control cables 360 degrees at the cabinet lead-
SV
through.
8. Ground the pair-cable shields of external control cables to a grounding clamp below
the control unit. Leave the other end of the shields unconnected or ground them
TR
indirectly via a high-frequency capacitor with a few nanofarads, eg, 3.3 nF / 630 V.
9. Connect the conductors to the appropriate terminals of the control unit.
ZH
10. Wire the optional modules if included in the delivery.
11. Connect the control panel cable to connector X13.
12. Put the control panel holder on the control unit. Put the control panel to the recess if
removed.
Task (input cables)
90
and Guidelines for planning the cabinet installation in the
Figure
Page
-
-
-
-
R
89
S
89
T
89
U
90
V
90