3.3.4 Factory setting 
 
The charger's factory settings are: 
 
 
 
           Sealed type battery (lead sealed)  
           BOOST in ON position 
           REFRESH in OFF position 
 
 
 
 
This setting is a compromise for a satisfactory recharging of different technologies of mixed or not batteries : 
 
Opened classic lead 
Sealed, Gel or AGM 
Spiral sealed 
 
To refine the load, please refer to the chart, paragraph : 3.3.2.  
 
The installer should set the switches (excluding input and output voltage) and possibly adjust the output voltage with 
no load using potentiometer R432 (use the appropriate tool to turn the screw of the potentiometer), depending on : 
 
the type of battery (contact the battery manufacturer if necessary) 
the intended usage 
the cross‐section and length of the output cables 
whether or not the boost function is required 
 
For special batteries, call in a professional installer, who will make the specific settings in accordance with the battery 
manufacturer's specifications and according to the specifics of the installation. 
 
 
CRISTEC disclaims any liability in case of damage to batteries or ineffective recharging. 
 
 
 