INSTALLATION 
 
This paragraph deals with installation‐related arrangements.  
 
Installation  and  initial  commissioning  should  be  carried  out  by  an  electrician  or  professional  installer  in  accordance 
with the standards currently in force (for pleasure boats the applicable international standard is ISO13297). 
 
The installer should familiarize himself with this operating manual and inform users of the instructions for use and the 
safety warnings set out in the manual. 
 
3.1
C
HARGER OVERALL DIMENSIONS
 
Chargers YPO 12‐16, 12‐25 and 24‐12 ‐ See appendix 3 
Chargers YPO 12‐40 and 24‐20 ‐ See appendix 4 
Chargers YPO 12‐60 and 24‐30 ‐ See appendix 5 
 
3.2
W
 
IRING
 
When  connecting  or  disconnecting  a  cable,  the  charger's  power  supply  must  be  off  and  the  batteries  electrically 
insulated from the charger. 
The references for additional supplies required for the appliance to operate efficiently are provided in the following 
paragraphs : failure to comply with these provisions renders the warranty null and void. 
 
3.2.1 Cable from the public AC power supply network or generator 
 
Disconnect AC network before any wiring and connecting of the connector. 
All YPOWER battery chargers can operate automatically and equally on single phase networks from 90 to 265VAC and 
from 47 to 65Hz. 
 
 
Generators 
The CRISTEC battery chargers are designed to operate from a generator.  
Be careful : In some cases, the generators can produce high over voltages, in particular during starting 
phase.  Before  connecting  the  charger,  please  check  its  compatibility  with  the  characteristics  of  the 
generator : power, voltage, overvoltage, frequency, current, etc. 
It's highly advised to disconnect the charger from the AC network during the generator starting phase. 
 
 
Depending on line lengths, the cross‐section of AC power cables must be at least equal to or greater than the values 
provided in the table below : 
 
Model 
YPO 12‐16, 12‐25 and 24‐12 
YPO 12‐40 and 24‐20 
YPO 12‐60 and 24‐30 
 
 
 
Minimum cross‐section for 
115VAC 
3 x 2.5 mm²  
 
Minimum cross‐section 
for 230VAC 
3 x 1.5 mm²  
3 x 1.5 mm²  
3 x 1.5 mm²  