3.2.3 Precautions regarding electromagnetic disturbance generated by the appliance
We recommend a minimum distance of 2m between the charger and any potentially sensitive equipment.
Use shielded cables for all the connections (*). The shielding should be earthed at both the transmitting and the
receiving ends.
Keep cable length and shielding connections down to a minimum.
Route cables as close as possible to conductive parts ("loose" cables or loops should be avoided – cables should be
flattened against conductive parts).
Keep power cables separate from battery cables.
Keep power cables separate from control cables (at least 200mm).
The cables should only supply power to this appliance; any branch‐off or short‐out intended to power another
appliance are prohibited.
(
)
*
This is a recommendation for installation rather than an obligation. The installing electrician should decide
whether or not to use shielded cable depending on the EMC environment.
3.2.4 Cabling principle
Typical installation
Such installation requires a GFCI (Ground Fault Circuit Interrupter), some appropriate fuses on batteries and battery
compartment temperature probe.
Other types of cabling ‐ see appendix 6.
27