3.2.3 Precautions regarding electromagnetic disturbance generated by the appliance 
 
We recommend a minimum distance of 2m between the charger and any potentially sensitive equipment. 
Use  shielded  cables  for  all  the  connections  (*).  The  shielding  should  be  earthed  at  both  the  transmitting  and  the 
receiving ends. 
Keep cable length and shielding connections down to a minimum. 
Route cables as close as  possible to conductive parts ("loose" cables or loops should be  avoided –  cables should  be 
flattened against conductive parts). 
Keep power cables separate from battery cables. 
Keep power cables separate from control cables (at least 200mm). 
The  cables  should  only  supply  power  to  this  appliance;  any  branch‐off  or  short‐out  intended  to  power  another 
appliance are prohibited. 
(
)
*
 
This is a recommendation for installation rather than an obligation. The installing electrician should decide 
whether or not to use shielded cable depending on the EMC environment. 
 
3.2.4 Cabling principle 
 
Typical installation 
 
Such installation requires a GFCI (Ground Fault Circuit Interrupter), some appropriate fuses on batteries and battery 
compartment temperature probe. 
 
 
 
Other types of cabling ‐ see appendix 6. 
 
 
 
27