3.3.2 Setting according to the batteries type
Switches setting
A
B
C
D
0
0
0
0
1
0
0
0
0
1
0
0
1
1
0
0
0
0
1
0
1
0
1
0
0
1
1
0
1
1
1
0
0
0
0
1
0
1
1
1
1
1
1
1
(*) Voltage on + BAT 1, + BAT 2 and + BAT E with 10% of the rated current and a tolerance of +/‐ 1%.
(
)
REFRESH is not advised for certain types of AGM batteries
**
Some specific settings are possible – please consult us.
3.3.3 Temperature compensation
The STP‐5M probe enables the compensation of Absorption voltage and
Floating Voltage depending on the ambient temperature of the battery room.
The adopted coefficient is ‐18mV/°C.
Description of the
battery type
Opened type bat
free electrolyte (wet)
Classic sealed type
bat
(Sealed Lead)
GEL type bat
AGM type bat**
Spiral type bat
Tin calcium lead bat
Wintering or standby
sealed bat
Stabilized DC power
supply
SPE1 open type bat
BUS CAN COMMUNICATION (available T2 2015)
BUS CAN COMMUNICATION (available T2 2015)
Voltage* with
Voltage* with
BOOST OFF
BOOST ON
13.4V
14.1V
13.8V
14.4V
FACTORY SETTING
13.8V
14.4V
13.6V
14.4V
13.6V
14.4V
14.4V
15.1V
13.4V
13.4V
12.0V
12.0V
13.2V
14.8V
Maximum
Maximum
duration of
duration of
BOOST at
ABSOPTION at
+/‐ 5% T
+/‐ 5% T
BOOST
2H
4H
2H
4H
2H
4H
2H
4H
2H
4H
2H
4H
0H
0H
0H
0H
ABS
29