3.2.2

Wiring Temperature Cable to Sensor

1. Locate Temperature Sensor terminal block TB1 connection screws.
2. Insert Temperature Sensor cable from transmitter into Junction Box gland.
Black
Orange
Brown
Red
Blue
Figure 3-8
Temperature Sensor Board to Junction Box Wiring
3. Connect Temperature Sensor PCB wires to Junction Box Sensor terminal board as
4. Replace Junction Box top cover.
5. Reinstall and hand-tighten four (4) Junction Box securing bolts. Using a torque wrench,
FUT1010 IP65 NEMA 4X & IP66 NEMA 7 Gas Quick Start
Operating Instructions, 1/2013, A5E02639183-AC
follows:
– Insert Black and Orange wires into lug (supplied), crimp lug and connect lug to TB1-1.
– Insert Brown and Red wires into lug (supplied), crimp lug and connect lug to TB1-2.
– Tie off Blue wire.
– Make sure all terminal block lug connections are hand-tight.
torque each bolt to 6.8 to 8.1 Nm (5 to 6 ft-lbs).
Short Terminals 1 and 4
Ground Terminals 2 and 3 to Terminal 5
1012EC Series Cable
Junction Box with cover removed
Temperature Sensor Connections: TB1-1
Black/Orange and TB1-2-Brown/Red. Tie off Blue