Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data; Scope Of Delivery; Accessories - Wilo -VeroLine-IPH-O Einbau- Und Betriebsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

5.2

Technical data

Property
Rated speed
Nominal diameters DN
Permissible min./max. fluid temperature
Max. ambient temperature
Maximum permissible operating pressure IPH-O:
Insulation class
Protection class
Pipe and pressure measurement connec-
tions
Approved fluids
Electrical connection
Motor special version
Motor protection
Speed control
Fluids
5.3

Scope of delivery

5.4

Accessories

Installation and operating instructions Wilo-VeroLine-IPH-O, IPH-W
Value
2900 or 1450 rpm
IPH-O: 20 to 80
IPH-W: 20 to 80
IPH-O: +20 °C to +350 °C
IPH-W: -10 °C to +210 °C
+40 °C
9 bar at max. +350 °C
IPH-W: 23 bar at max. +210 °C
F
IP 55
Tongue and groove flange PN25
(in accordance with DIN EN 1092-1)
Heating water according to VDI 2035
Water/glycol mixture up to 40 Vol.-%
Heat transfer oil
3~400 V, 50 Hz
3~230 V, 50 Hz
Special voltage/frequency
(on request)
Required onsite
Wilo control devices
When ordering spare parts, make sure to state all the information
given on the pump and motor rating plates.
If water/glycol mixtures with up to 40% glycol (or fluids with a differ-
ent velocity to pure water) are used, the pump data must be corrected
to match the higher viscosity, regardless of the percentage mixture
relationship and the fluid temperature. The motor power must also be
adjusted if necessary.
• Only use mixtures with corrosion inhibitors. The respective manufac-
turer's instructions are to be observed.
• The fluid must be sediment-free.
• Wilo's approval must be obtained for the use of other fluids.
NOTE
Always read and follow the material safety data sheet for the fluid
being pumped.
• IPH-W/O pump
• Installation and operating instructions
• Counter flange and seals
Accessories must be ordered separately:
• PTC thermistor tripping unit for switch cabinet installation
For a detailed list, consult the catalogue/price list.
English
Remarks
Standard version
Standard version
Standard version
Standard version
Alternative application for stand-
ard version (no additional charge)
Special version or auxiliary equip-
ment (at additional charge)
Standard version
Standard version
23

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Wilo-veroline-iph-w

Inhaltsverzeichnis