Diameter of connection pipe (mm)
Liquid pipe
Ø 6
Ø 6 or Ø 9,5
Ø 12
Ø 16
Ø 19
Ø 22,2
106
4. The calculation method of additional refrigerant oil and refrigerant charging
amount after prolonging connection pipe
After the length of connection pipe is prolonged for 10 m at the basis of standard
length, you should add 5ml of refrigerant oil for each additional 5 m of connection
pipe. The calculation method of additional refrigerant charging amount (on the basis
of liquid pipe):
• Additional refrigerant charging amount = prolonged length of liquid pipe ×
additional refrigerant charging amount per meter.
• Basing on the length of standard pipe, add refrigerant according to the requirement
as shown in the table. The additional refrigerant charging amount per meter is
different according to the diameter of liquid pipe.
Note: The information on the additional quantity of coolant is recommended and is
not mandatory.
Indoor unit throttle
Gas pipe
cooling and heating
Ø 9,5 or Ø 12
Ø 16 or Ø 19
Ø 19 or Ø 22,2
Ø 25,4 or Ø 31,8
X
X
Cooling only,
Cooling only
(g/m)
16
40
80
136
200
280
Outdoor unit throttle
Cooling and
(g/m)
heating (g/m)
12
16
12
40
24
96
48
96
200
200
280
280